Delta Din-rail Power Meter DPM-D520I User
Manual
5-10
_5
5F
40096
Pickup setpoint (total
active power value
exceeding this value
triggers alarm)
0.000 – 99999.999
float
kW
4
R/W
60
40097
61
40098
Pickup time delay
(alarm–trigger delay) 0 – 99
word
s
2
R/W
62
40099 Dropout setpoint (total
active power value
below this value
clears alarm)
0.000 – 99999.999
float
kW
4
R/W
63
40100
64
40101
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Over Reactive Power
65
40102 Alarm enable
0: Disable
1: Enable
word
2
R/W
66
40103
Pickup setpoint (total
reactive power value
exceeding this value
triggers alarm)
0.000 – 99999.999
float kVAR
4
R/W
67
40104
68
40105
Pickup time delay
(alarm–trigger delay) 0 – 99
word
s
2
R/W
69
40106
Dropout setpoint (total
reactive power value
below this value
clears alarm)
0.000 – 99999.999
float kVAR
4
R/W
6A
40107
6B
40108
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over Apparent Power
6C
40109 Alarm enable
0: Disable
1: Enable
word
2
R/W
Содержание DPM-D520I
Страница 3: ......
Страница 9: ...Delta Din rail Power Meter DPM D520I User Manual 1 4 _1 _1 MEMO...
Страница 15: ...Delta Din rail Power Meter DPM D520I User Manual 2 6 _2 MEMO...
Страница 31: ...Delta Din rail Power Meter DPM D520I User Manual 4 10 _4 MEMO...
Страница 116: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...
Страница 119: ...Delta Din rail Power Meter DPM D520I User Manual 6 4 _6 Memo...
Страница 120: ...A 1 Appendix A Accessories Table of Contents A 1 DCT1000 Series A 2 A 2 DCT2000 Series A 4 12 A...
Страница 125: ...Delta Din rail Power Meter DPM D520I User Manual A 6 _A _1 _1 MEMO...