Chapter 5 Parameters and Functions
5-9
_5
52
40083
value exceeding this
value triggers alarm)
53
40084
Pickup time delay
(alarm–trigger delay) 0 – 99
word
s
2
R/W
54
40085
Dropout setpoint (over
voltage unbalance
value below this value
clears alarm)
0.00 – 99.99
float
%
4
R/W
55
40086
56
40087
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over Current Unbalance
57
40088 Alarm enable
0: Disable
1: Enable
word
2
R/W
58
40089
Pickup setpoint (over
current unbalance
value below this value
triggers alarm)
0.00 – 99.99
float
%
4
R/W
59
40090
5A
40091
Pickup time delay
(alarm–trigger delay) 0 – 99
word
s
2
R/W
5B
40092
Dropout setpoint (over
current unbalance
value exceeding this
value clears alarm)
0.00 – 99.99
float
%
4
R/W
5C
40093
5D
40094
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over Active Power
5E
40095 Alarm enable
0: Disable
1: Enable
word
2
R/W
Содержание DPM-D520I
Страница 3: ......
Страница 9: ...Delta Din rail Power Meter DPM D520I User Manual 1 4 _1 _1 MEMO...
Страница 15: ...Delta Din rail Power Meter DPM D520I User Manual 2 6 _2 MEMO...
Страница 31: ...Delta Din rail Power Meter DPM D520I User Manual 4 10 _4 MEMO...
Страница 116: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...
Страница 119: ...Delta Din rail Power Meter DPM D520I User Manual 6 4 _6 Memo...
Страница 120: ...A 1 Appendix A Accessories Table of Contents A 1 DCT1000 Series A 2 A 2 DCT2000 Series A 4 12 A...
Страница 125: ...Delta Din rail Power Meter DPM D520I User Manual A 6 _A _1 _1 MEMO...