Chapter 4 Operation
4-3
4_
4.2
Basic Setups
4.2.1
Set up the Time and Date
Time:
Present power meter time; the time format includes the hour, minute, and second.
Date:
Present power meter date; the date format includes the last two digits of the year, month, date and
day.
4.2.2
Communication Settings
Address:
The range of address for the device is 1~254, with the broadcast address of 255 and factory default is 1.
Corresponding Modbus address 0x1B.
Protocol:
Mode of communication transmission, with a selection from RTU (factory default), ASCII. Corresponding
Modbus address 0x17.
Baud Rate:
Speed of communication transmission, with the factory default of 9600 kbps. Corresponding Modbus
address 0x16.
Parity:
Odd and even checking bit for communication, with a selection from None (factory default), Even, and
Odd. Corresponding Modbus address 0x19
Stop Bit:
Signal for completion of packet transmission, with a selection from 1 and 2 bit(s) (factory default: 1 bit).
Corresponding Modbus address 0x1A.
USER / SETUP Mode:
Mode
Uses and Timing
USER
Under normal status of meter communication.
SETUP
When the original communication parameters are lost and need to be reset.
Setup steps for SETUP mode:
1. Switch the Setup switch to
SETUP
mode.
Содержание DPM-D520I
Страница 3: ......
Страница 9: ...Delta Din rail Power Meter DPM D520I User Manual 1 4 _1 _1 MEMO...
Страница 15: ...Delta Din rail Power Meter DPM D520I User Manual 2 6 _2 MEMO...
Страница 31: ...Delta Din rail Power Meter DPM D520I User Manual 4 10 _4 MEMO...
Страница 116: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...
Страница 119: ...Delta Din rail Power Meter DPM D520I User Manual 6 4 _6 Memo...
Страница 120: ...A 1 Appendix A Accessories Table of Contents A 1 DCT1000 Series A 2 A 2 DCT2000 Series A 4 12 A...
Страница 125: ...Delta Din rail Power Meter DPM D520I User Manual A 6 _A _1 _1 MEMO...