Delta Din-rail Power Meter DPM-D520I User
Manual
4-6
_4
4.2.6
Set up the Demands
Method:
Block interval demand method is supported for demand calculation. Corresponding Modbus
address is 0x1D.
Interval:
Time interval to calculate for the demand, with a selectable range of 1~60 min (factory default is
1 min). Corresponding Modbus address is 0x1E.
4.2.7
Set up the Resets
There are seven types of supported resets, including Default, Energy, Demand, Alarm, MaxMin, Data Log, and
ClearAll.
Default:
Restore all the settings back to the defaults.
Energy:
Clear all the accumulated and auto-read energy values.
Demand:
Clear the current demand, power factor demand, recorded time and date.
Alarm:
Clear all the detected alarm logs.
MaxMin:
Clear all maximum values and minimum value logs.
Data Log:
Clear the data log stored in the memory.
Clear All:
Restore all the settings back to the defaults and clear all logs.
The corresponding MODBUS address is 0x1C.