Click the Device Assignment under Driver folder in the Navigation Area. Assign the netX Driver to the
detected COMX module by checking the checkmark box next to the detected device, and click Apply:
Note
When used with Turbo PMAC, the reset line is released too fast for
some Hilscher COMX modules, which puts them in a boot mode.
This can prevent the device from being detected by Sycon.NET
software. Make sure the device receives a system wide reset using the
PMAC suggested M-variables ulSystemCommandCOS and
HSF_RESET registers as shown here.
SCtrl_ulSystemCommandCOS=$55AA55AA
HCSC_HSF_RESET=1
Note that ACC-72EX Setup Assistant software automatically resets
the cards if it cannot detect the identification cookie.