34
The following screen will appear:
This page shows the
% Outside Air
result and the
Ventilation Rate
value.
The captured data can be saved in the memory by pressing MEM.
MEASURE: CO
2
Outdoor 400 ppm
Supply 660 ppm
Return 850 ppm
FVm 260 L/s
occupants No. 10
%Outdoor Air 42.2 %
Air changes:
10.9 (L/s)/p
<MEM>save <ESC>exit