3.5 Electrical Installation for AC
3.5.1 Required Protective Devices and Cable Cross-sections
The AC cable must be jacked and meet the specifications in
Table 3-1
.
Please use the proper upstream circuit breaker to protect the unit.
Important information regarding safety
-Always follow the specific regulations of your country or region.
-Always follow the specific regulations of your energy provider.
-Install all stipulated safety and protective devices (e.g. automatic circuit breakers
and/or surge protection devices).
Table 3-1 : AC input cable requirement
Model
Current Rating
Wire Size
25 A
BX6.3/12.6_AC100
3 - 5 mm
2
Max.Cable Overall Diameter
22 mm
Table 3-2 : Upstream circuit breaker
Model
Current Rating
16 A
BX6.3_AC100
25 A
BX12.6_AC100
3.5.2 AC Connection
Areas outside Australia and New Zealand, it recommended to connect AC wiring
as shown in
Figure 3-10
. The connection between Grid N and Load N is used to
eliminate the floating voltage between Load N and PE.
However, BX6.3_AC100 can still works without the Grid N and Load N connection.
Figure 3-10 : Storage system operation illustration
PE
PE
L
N
N
L
N
L
RCD
Backup Power loads
AC load
Distribution Panel
Grid
Load
L
N
PE
L
N
28