3.5.4 AC plug error check
Check the cable correction of AC plug by following instructions when error code:
AC phase abnormal (E08)
appear.
Step1.
Check the connection of each cable from AC panel.
Step2.
Check the foolproof brick on socket and AC plug is located correct.
Step3.
Check the continuity between N(Grid) and N(Load).
PE
N
1
2
L
AC plug side (print)
AC panel side
PE
N (Grid)
L (Load)
N (Load)
L (Grid)
N (Load)
L (Grid)
N (Load)
L (Grid)
Socket
AC plug
32
Installation