Device Volume
Multi-
State
Value
4
1: High
2: Medium
3: Low
1, 2, 3
R/W
Device volume control
High
Relay1 Polarity
Multi-
State
Value
5
1: Normally
Open
2: Normally
Closed
3: Disabled
1, 2, 3
R/W
Relay out polarity status when
not active
Normally
Open
Relay2 Polarity
Multi-
State
Value
6
1: Normally
Open
2: Normally
Closed
3: Disabled
1, 2, 3
R/W
Relay out polarity status when
not active
Normally
Open
Relay3 Polarity
Multi-
State
Value
7
1: Normally
Open
2: Normally
Closed
3: Disabled
1, 2, 3
R/W
Relay out polarity status when
not active
Normally
Open
Relay1
Functionality
Multi-
State
Value
8
1: Sash Alarm
2: Flow Alarm
3: Light
4: Fan
5: Null
1, 2, 3, 4, 5
R/W
Relay functionality
Flow Alarm
Relay2
Functionality
Multi-
State
Value
9
1: Sash Alarm
2: Flow Alarm
3: Light
4: Fan
5: Null
1, 2, 3, 4, 5
R/W
Relay functionality
Sash Alarm
Relay3
Functionality
Multi-
State
Value
10
1: Sash Alarm
2: Flow Alarm
3: Light
4: Fan
5: Null
1, 2, 3, 4, 5
R/W
Relay functionality
Null
Ringback Delay
Multi-
State
Value
11
1: Off
2: 10 s
3: 30 s
1, 2, 3, 4, 5, 6
R/W
Time delay before audible alarm
returns, after pressing the mute
button
10 sec