Rooster™
Sensor200 USER MANUAL
Rooster™
Sensor200 USER MANUAL 62360MN000-A00
29 of 40
Feature
Object
Type
Device
Instance
Units
Range
Read/
Write
Definition
Default
Value
Notes
Calibration
Status
Binary
Input
0
0: Uncalibrated
1: Calibrated
0, 1
R
Calibration status
Calibrated
Low Flow Alarm Binary
Input
1
0: Inactive
1: Active
0, 1
R
Low Flow Alarm becomes active
if low flow alarm setpoint is
reached
High Flow
Alarm
Binary
Input
2
0: Inactive
1: Active
0, 1
R
High Flow Alarm becomes active
if high flow alarm setpoint is
reached
Allowed
Turbulence
Binary
Input
3
0: Normal
1: High
0, 1
R
Allowed turbulence level during
calibration
Normal
Setting Allowed Turbulence to
High will help you overcome
cabinet-level airflow instability
issues. It should be reserved for
rare circumstances where there is
difficulty achieving stable, laminar
airflow.
Sash
Calibration
Status
Binary
Input
4
0: Uncalibrated
1: Calibrated
0, 1
R
Sash calibration status
Uncalibrated Sash calibration is associated
with Sash Type analog
Relay1 Status
Binary
Input
5
0: OFF
1: ON
0,1
R
Current output status of Relay 1
-
Relay2 Status
Binary
Input
6
0: OFF
1: ON
0,1
R
Current output status of Relay 2
-
Relay3 Status
Binary
Input
7
0: OFF
1: ON
0,1
R
Current output status of Relay 3
-
Sash In Status
Binary
Input
8
0: OFF
1: ON
0,1
R
Sash input status
NSB In Status
Binary
Input
9
0: OFF
1: ON
0,1
R
NSB input status
Aux In Status
Binary
Input
10
0: OFF
1: ON
0,1
R
Aux input status