DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
32
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
6.2.1 LIST OF ADJUSTABLE PARAMETERS IN ‘MAIN CONFIGURATION EDITOR’
Section
Parameter
Display shows
Values
Input settings
Low Oil Pressure warning
Oil pressure pre-alarm
0-4bar (
1.17bar
)
Low Oil Pressure shutdown
Oil pressure shutdown
0-4bar (
1.03bar
)
High Temperature warning
Coolant temp pre-alarm
80-140
°
C (
110
°
C
)
High Temperature shutdown
Coolant temp shutdown
80-140
°
C (
120
°
C
)
Low Coolant Temperature
Low Coolant Temperature
65-136
°
C (65
°
C)
Timers
Mains transient delay
Mains transient delay
0-10s (
2s
)
Generator transient delay
Gen transient delay
0 -10s (
0s
)
Start delay
Start delay
0 -60m (
5s
)
Return delay
Return delay
0 -60m (
30s
)
Preheat
Preheat
0 -60m (
5s
)
Crank attempt
Cranking time
0 -60s (
10s
)
Crank rest
Crank rest
0-60s (
10s
)
Safety delay
Safety on
0-30s (
10s
)
Overspeed overshoot
Overspeed overshoot
0-10s (
0s
)
Warming up
Warm up
0-60m (
0s
)
Transfer delay
Transfer delay
0-10m (
1s
)
Cooling run
Cooling
0-60m (
60s
)
Fail to stop delay
Fail to stop
0-30s (
30s
)
Low battery volts delay
Battery low delay
0-10m (
30s
)
High battery volts delay
Battery high delay
0-10m (
30s
)
Mains (utility)
Mains Low Voltage
Mains undervolt trip
50-360V ph-N (
184V
)
Mains High Voltage
Mains overvolt trip
50-360V ph-N (
276V
)
Mains Low Frequency
Mains low frequency trip
0 -75Hz (
45Hz)
Mains High Frequency
Mains high frequency trip
0 -75Hz (
55Hz
)
Generator
Generator Under voltage shutdown
Gen low voltage shutdown
50-360V ph-N (
184V
)
Generator Under voltage prealarm
Gen low voltage pre-alarm
50-360V ph-N (
196V
)
Generator Over voltage prealarm
Gen high voltage pre-alarm
50-360V ph-N (
253V
)
Generator Over voltage shutdown
Gen high voltage shutdown
50-360V ph-N (
265V
)
Generator Under frequency shutdown
Gen low frequency shutdown
0 -75Hz (
40Hz
)
Generator Under frequency prealarm
Gen low frequency pre-alarm
0 -75Hz (
42Hz
)
Generator Over frequency prealarm
Gen high frequency pre-alarm
0 -75Hz (
55Hz
)
Generator Over frequency shutdown
Gen high frequency shutdown
0 -75Hz (
57Hz
)
Generator delayed overcurrent
Delayed high current
50-120% (
100%
)
Engine
Underspeed (RPM) shutdown
Underspeed shutdown
0-6000RPM (
1270
)
Underspeed (RPM) warning
Underspeed pre-alarm
0-6000RPM (
1350
)
Overspeed (RPM) warning
Overspeed pre-alarm
0-6000RPM (
1650
)
Overspeed (RPM) shutdown
Overspeed shutdown
0-6000RPM (
1710
)
Overspeed overshoot %
Overspeed overshoot percent
0-10 (
0%
)
Low DC Voltage
Battery low warning
0-24V (
8V
)
High DC Voltage
Battery high warning
0-24V (
33V
)
Charge Alternator Failure
Charge fail warning
0-24V (
6V
)
Display
Language
Language
ENGLISH
, OTHER
(see note below)
Application
Engine speed selection
Alternative Frequency
Disable,
Enable
Volts selection
Alternative Voltage
Disable,
Enable
Wiring topography
AC System
3 phase 4 wire
Single phase, 2 wire
3 phase, 3 wire
2 phase 3 wire (L1 & L2)
2 phase 3 wire (L1 & L3)
Full load current rating
Generator Full Load
5A - 6000A
(500A)
Droop
Disable,
Enable
Droop %
0%
- 5%
LCD Contrast
Contrast
|
Date/Time
Date and Time
dd mmm yyyy hh:mm
NOTE:- Display language selection via the modules front panel configuration editor is between
English and a PC configurable language. This ‘other’ language is configurable using the 5xxx PC
configuration software in conjunction with the P810 interface.
NOTE:- Droop percent is only applicable to CAN controlled engines when CAN is enabled in the
5300 series controller.