![Deep Sea Electronics Plc DSE5320 Скачать руководство пользователя страница 29](http://html.mh-extra.com/html/deep-sea-electronics-plc/dse5320/dse5320_operating-manual_2463100029.webp)
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
29
6 FRONT PANEL CONFIGURATION
This configuration mode allows the operator limited customising of the way the module operates.
Operation
Detail
To enter the
‘configuration mode’
press both the
INFO
and
STOP
buttons together.
+
6.1.1 ENTERING THE CONFIGURATION EDITOR PIN NUMBER
The configuration editor contains two sections.
•
Main configuration editor (for ‘site adjustable’ or ‘commissioning’ parameters)
•
Application editor (to allow installation engineers to make application changes).
The ‘Application Editor’ is designed to allow the module to be configured for different applications without
needing to re-configure the module settings. This makes it particularly suitable for applications where the
generator would be used in a number of different roles, specifically in Rental or mobile type applications.
If the module PIN number has been set, the PIN number request is then shown. The configuration cannot be
viewed or changed until the PIN number is correctly entered.
Enter either the ‘main’ PIN or the application PIN.
If no PIN has been set, then skip to the next section.
NOTE:- The ‘Application Editor’ must be enabled first in order to make it accessible from the
module’s fascia. This is done by setting a PIN (number) for the module’s main front panel editor, using the
5xxx for Windows™ PC configuration software.
Deep Sea Electronics
Model 5220
O
I
+
AUTO
i
Warming 10s
L-N 240V 0A 50Hz
L-L 415V 0kW
RUNNING IN AUTO
- button
+ button
9
button
The configuration editor contains two sections.
•
Main configuration editor (for ‘site adjustable’ or ‘commissioning’ parameters)
•
Application editor (to allow installation engineers to make application changes).
The ‘Application Editor’ is designed to allow the module to be configured for different applications without
needing to re-configure the module settings. This makes it particularly suitable for applications where the
generator would be used in a number of different roles, specifically in Rental or mobile type applications.