DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual 

 

Part No. 057-014    5320 OPERATING MANUAL ISSUE 5.1    18/06/2007 ADM   

13 

 
AUXILIARY INPUTS

, auxiliary inputs can be user configured and will display the message as written by the user. 

 

Example 

Alarm

 

Warning 

Bearing temp high 

 

LOW FUEL LEVEL. 

will be displayed if the fuel level detected by the fuel level sender falls below the low fuel level 

setting. 

 

Alarm

 

Warning 

Low fuel level 

 

CAN ECU ERROR 

If the module is configured for 

CAN instruments

 and receives an “error” message from 

the engine control unit, ‘Can ECU error” is shown on the module’s display and a warning alarm is generated. 

 

Example 

Alarm 

The display will alternate 
between the text display and the 
manufacturers error codes

 

Alarm

 

Can ECU error 

Exhaust high 

temperature 

Can ECU error 

SPNnnnnnnn 

FMInnnnnnn 

 

4.2 ANALOGUE 

PRE-ALARMS 

 

The following alarms are termed ‘pre-alarms’ as they pre warn the operator of a potentially more serious alarm 
condition. For instance, if the engine temperature rises past the pre alarm level, a warning condition will occur to 
notify the operator. If the temperature falls below this level, then the alarm ceases, and the set will continue to run 
as normal. However if the temperature continues to rise until the coolant temperature trip point is reached, the 
warning is escalated and a high coolant temperature shutdown is initiated. 

 

LOW OIL PRESSURE

, if the module detects that the engine oil pressure has fallen below the low oil pressure pre-

alarm setting level after the 

Safety On

 timer has expired, a warning will occur.  Alarm Warning Low Oil Pressure 

will be displayed. 

 

Alarm

 

Warning 

Low oil pressure 

 

HIGH ENGINE TEMPERATURE

 if the module detects that the engine coolant temperature has exceeded the high 

engine temperature pre-alarm setting level after the 

Safety On

 timer has expired, a warning will occur.  Alarm 

Warning High Coolant Temperature will be displayed. 

 

Alarm

 

Warning 

High temperature 

 

LOW ENGINE TEMPERATURE

 if the module detects that the engine coolant temperature has fallen below the low 

engine temperature pre-alarm setting level after the 

Safety On

 timer has expired, a warning will occur.  Alarm 

Warning Low Coolant Temp will be displayed. 

 

Alarm

 

Warning 

Low Coolant Temp 

 

CALL US TODAY 

1-888-POWER-58

REQUEST A QUOTE 

[email protected]

SHOP ONLINE 

www.genpowerusa.com

Содержание DSE5320

Страница 1: ...OMPLEX SOLUTIONS MADE SIMPLE DEEP SEA ELECTRONICS PLC DSE5320 AUTO MAINS FAILURE MODULE OPERATING MANUAL CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com ...

Страница 2: ...form including photocopying or storing in any medium by electronic means or other without the written permission of the copyright holder except in accordance with the provisions of the Copyright Designs and Patents Act 1988 Applications for the copyright holder s written permission to reproduce any part of this publication should be addressed to Deep Sea Electronics Plc at the address above Any re...

Страница 3: ...ENT 25 5 2 3 GSM MODEM STATUS 26 5 2 4 CAN ERROR MESSAGES 27 5 3 VIEWING THE EVENT LOG 27 5 4 USER CONFIGURABLE INDICATORS 28 5 5 CONTROLS 28 6 FRONT PANEL CONFIGURATION 29 6 1 1 ENTERING THE CONFIGURATION EDITOR PIN NUMBER 29 6 2 EDITING A VALUE 31 6 2 1 LIST OF ADJUSTABLE PARAMETERS IN MAIN CONFIGURATION EDITOR 32 6 2 2 LIST OF ADJUSTABLE PARAMETERS IN APPLICATION EDITOR 33 6 2 3 EDITING THE CUR...

Страница 4: ...E 56 14 1 3 2 PHASE 3 WIRE 2 PHASE CENTRE TAP NEUTRAL 56 14 2 ICONS AND LCD IDENTIFICATION 57 14 2 1 PUSH BUTTONS 57 14 2 2 STATUS MEASUREMENT UNITS 57 14 2 3 LED INDICATION 57 14 3 5320 IDMT TRIPPING CURVES TYPICAL 58 14 4 SENDER WIRING RECOMMENDATIONS 59 14 4 1 EARTH RETURN SENDERS 59 14 4 2 INSULATED RETURN SENDERS 59 14 4 3 FUEL LEVEL SENDERS 59 14 5 CAN INTERFACE 61 14 6 OUTPUT EXPANSION 61 1...

Страница 5: ...as standard Text based LCD display supporting multiple languages Voltage Current and Power monitoring Engine parameter monitoring Fully configurable inputs for use as alarms or a range of different functions Extensive range output functions using built in relay outputs or relay expansion available Selective operational sequences timers and alarm trips can be altered by the customer via a PC using ...

Страница 6: ...nces followed by a module containing the standard factory configuration Always refer to your configuration source for the exact sequences and timers observed by any particular module in the field Deep Sea Electronics Model 5220 O I AUTO i Warming 10s L N 240V 0A 50Hz L L 415V 0kW RUNNING IN AUTO FIG 1 CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa co...

Страница 7: ...ing auxiliary output if configured will energise NOTE If the mains supply returns within limits or the Remote Start signal is removed if the start sequence was initiated by remote start during the Start Delay timer the unit will return to a stand by state After the above delays the Fuel Solenoid or enable ECU output if configured is energised then one second later the Starter Motor is engaged NOTE...

Страница 8: ...A load transfer will not be initiated until the Oil Pressure has risen Thus preventing excessive wear on the engine On the return of the mains supply or removal of the Remote Start signal if the set was started by remote signal the Stop delay timer is initiated once it has timed out the load Transfer signal is de energised removing the load The Cooling timer is then initiated allowing the engine a...

Страница 9: ...engaged and locked out at a pre set frequency from the Alternator output Alternatively a Magnetic Pickup mounted on the flywheel housing can be used for speed detection This is selected by PC using the 5xxx series configuration software Rising oil pressure can also be used to disconnect the starter motor however it cannot be used for underspeed or overspeed detection NOTE If the unit has been conf...

Страница 10: ...ill be displayed Alarm Shutdown Failed to start When the engine fires the starter motor is disengaged and locked out at a pre set frequency from the Alternator output Alternatively a Magnetic Pickup mounted on the flywheel housing can be used for speed detection This is selected by PC using the 5300 series configuration software Rising oil pressure can also be used to disconnect the starter motor ...

Страница 11: ...emperature shutdown Emergency Stop and Low Coolant Warning alarms have been triggered These will automatically scroll round in the order that they occurred Running in auto If no alarms are present the LCD will display this default page Generator on load L N 230V 240A 50Hz L L 400V 133kW In the event of a warning alarm the LCD will display the appropriate text If a shutdown then occurs the module w...

Страница 12: ... LOW VOLTAGE will be displayed if the module detects that the plant DC supply has fallen below the low volts setting level The Battery Low Voltage alarm is delayed by the Low DC Volts Delay timer Alarm Warning Low battery volts BATTERY HIGH VOLTAGE will be displayed if the module detects that the plant DC supply has risen above the high volts setting level The Battery High Voltage alarm is delayed...

Страница 13: ...ill occur to notify the operator If the temperature falls below this level then the alarm ceases and the set will continue to run as normal However if the temperature continues to rise until the coolant temperature trip point is reached the warning is escalated and a high coolant temperature shutdown is initiated LOW OIL PRESSURE if the module detects that the engine oil pressure has fallen below ...

Страница 14: ...fety On timer has expired a warning is initiated Alarm Warning Low Frequency will be displayed Alarm Warning Under frequency GENERATOR HIGH VOLTAGE if the module detects a generator output voltage in excess of the pre set pre alarm a warning is initiated Alarm Warning High voltage will be displayed it is an immediate warning Alarm Warning AC Overvolts GENERATOR LOW VOLTAGE if the module detects a ...

Страница 15: ...pressure will be low with the engine at rest FAIL TO START if the engine does not fire after the pre set number of attempts has been made a shutdown will be initiated Alarm Shutdown Fail To Start will be displayed Alarm Shutdown Failed to start EMERGENCY STOP removal of the Positive DC Supply from the Emergency Stop input initiates the following sequence firstly it will initiate a controlled shutd...

Страница 16: ...ware manual under heading Overspeed Overshoot for details UNDERSPEED if the engine speed falls below the pre set trip after the Safety On timer has expired a shutdown is initiated Alarm Shutdown Underspeed will be displayed Alarm Shutdown Underspeed GENERATOR HIGH FREQUENCY if the module detects a generator output frequency in excess of the pre set trip a shutdown is initiated Alarm Shutdown High ...

Страница 17: ...RY INPUTS if an auxiliary input has been configured as a shutdown the appropriate message will be displayed as configured by the user Alarm Shutdown Bearing temp high LOSS OF SPEED SIGNAL if the speed sensing signal is lost during cranking a shutdown is initiated Alarm Shutdown Loss Of Speed Signal will be displayed Alarm Shutdown Loss of speed signal NOTE This will only occur if the speed sensing...

Страница 18: ...nitiated This warning will continue for a period of time depending upon the level of overload that the generator is subjected to and the configuration setting for Generator High Current in the 5xxx series configuration software Alarm Shutdown High current trip For instance the factory default settings for Generator High Current allow for a loading of the generator to 110 for one hour That is to sa...

Страница 19: ...d the fault removed to reset the module AUXILIARY INPUTS if an auxiliary input has been configured as an electrical trip the appropriate message will be displayed as configured by the user Example Alarm Electrical trip Phase rotation GENERATOR HIGH CURRENT If the module detects a generator output current in excess of the pre set trip a warning is initiated If this high current condition continues ...

Страница 20: ...ollowing section details the function and meaning of the various controls on the module Scroll Down Next page Configurable LEDs Deep Sea Electronics Model 5220 O I AUTO i Warming 10s L N 240V 0A 50Hz L L 415V 0kW RUNNING IN AUTO Stop Manual Test Auto Mute Lamp Test Start FIG 2A CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com ...

Страница 21: ...input configured for Generator closed auxiliary The LED will be lit when the generator closed auxiliary input is active The LED shows the state of the auxiliary contact 2 There is NO input configured for Generator closed auxiliary factory default setting The LED will be lit when the 5320 gives the loading signal to the generator The LED shows the state of the 5320 s loading request 3 Digital input...

Страница 22: ... of the 3 phase currents generator frequency average line to line voltage and total kilo Watts Generator on load L N 230V 240A 50Hz L L 400V 133kW 5 1 2 TYPICAL INSTRUMENT DISPLAY Coolant temperature The display of coolant temperature in both degrees centigrade and Fahrenheit 60 ºC 140 ºF Oil pressure The display of engine oil pressure in Bar Pounds Per Square Inch and kilo Pascal 6 Bar 87 PSI 600...

Страница 23: ...xt page i button Page order Status display Instrument display Alarms display Event log It is possible to manually scroll to display the different instruments by repeatedly operating the next page button Once selected the instrument will remain on the LCD display until the user selects a different instrument or after a period of inactivity for the duration of the configurable Page Timer the module ...

Страница 24: ... feed and the module is suitably configured Displays mains load when CTs are located in the load feed and the module is suitably configured Generator Output Number of starts Fuel level Mains Utility AC Voltage Line Neutral Mains Utility AC Voltage Line Line Mains Utility Frequency Hz If enhanced instrumentation is selected the following instrumentation will become available if supported by the eng...

Страница 25: ...ressing the DOWN button the LCD will then show Oil pressure Oil pressure 6 Bar 87 PSI 600 KPa Pressing the button again will scroll through each individual instrument eventually returning to the original instrument displayed NOTE Once selected the instrument will remain on the LCD display until the user selects a different instrument or after a period of inactivity for the duration of the configur...

Страница 26: ...operating correctly this procedure begins again from Resetting modem and will continue to repeat until the modem operation is detected correctly Modem Status The modem has been initialised and is ready to answer OK shows The SIM card is inserted but there is no signal Ready to answer OK Modem Status The modem has been initialised and is ready to answer The SIM card is inserted the signal is receiv...

Страница 27: ...nstructions provided by the engine manufacturer or contact the engine manufacturer for further assistance NOTE For further details on connection to electronic engines please refer to the CAN and DSE wiring manual 5 3 VIEWING THE EVENT LOG The 53xx modules maintains a log of the last 30 shutdown alarms and mains fail returns to enable the operator or engineer to view the past alarms history Only sh...

Страница 28: ...s Automatic mode This mode allows the module to control the function of the generator automatically The module will monitor the remote start input and the mains supply If the remote start input is active or the mains fails the set will be automatically started and placed on load Close Generator becomes active if used If the starting signal is removed or the mains returns the module will automatica...

Страница 29: ...equest is then shown The configuration cannot be viewed or changed until the PIN number is correctly entered Enter either the main PIN or the application PIN If no PIN has been set then skip to the next section NOTE The Application Editor must be enabled first in order to make it accessible from the module s fascia This is done by setting a PIN number for the module s main front panel editor using...

Страница 30: ...hird digit of the PIN number Press 9 when the third digit is correctly entered The entered digit will turn back to a to maintain security Enter pin The fourth is now flashing Press or buttons to adjust it to the correct value for the fourth digit of the PIN number Press 9 when the fourth digit is correctly entered NOTE When 9 is pressed after editing the final PIN digit the PIN is checked for vali...

Страница 31: ... pressure will start to flash Pressing the or buttons will adjust the parameter to the desired value In this example the 30 PSI will be adjusted and the bar kPA units will automatically show their respective values 2 Bar 30 PSI 200 kPa Oil pressure pre alarm Press the 9 button to save the value The value will stop flashing to confirm that it has been saved 3 Bar 45 PSI 300 kPa Oil pressure shutdow...

Страница 32: ...high voltage pre alarm 50 360V ph N 253V Generator Over voltage shutdown Gen high voltage shutdown 50 360V ph N 265V Generator Under frequency shutdown Gen low frequency shutdown 0 75Hz 40Hz Generator Under frequency prealarm Gen low frequency pre alarm 0 75Hz 42Hz Generator Over frequency prealarm Gen high frequency pre alarm 0 75Hz 55Hz Generator Over frequency shutdown Gen high frequency shutdo...

Страница 33: ...election Alternative Frequency Disable Enable Volts selection Alternative Voltage Disable Enable Wiring topography AC System 3 phase 4 wire Single phase 2 wire 3 phase 3 wire 2 phase 3 wire L1 L2 2 phase 3 wire L1 L3 Full load current rating Generator Full Load 5A 6000A 500A Droop Disable Enable Droop 0 5 LCD Contrast Contrast Date Time Date and Time dd mmm yyyy hh mm CALL US TODAY 1 888 POWER 58 ...

Страница 34: ...nt log Date and time Press the Stop Reset and Info i buttons simultaneously If the module PIN number has been set the PIN number request is then shown The configuration cannot be viewed or changed until the PIN number is correctly entered see the section ACCESSING THE FRONT PANEL CONFIGURATION EDITOR Press the button until the desired page is shown Date and time 19 Sep 2005 10 00 Date and time To ...

Страница 35: ... and select the year for adjustment The year will start to flash Pressing the or buttons will adjust the year to the desired value 19 Sep 2005 10 00 Date and time Press the 9 button to save the values 19 Sep 2005 10 00 NOTE To exit the front panel configuration editor at any time press the Stop Reset button Ensure you have saved any changes you have made by pressing the 9 button first Continuing t...

Страница 36: ...should be mounted on suitable anti vibration mountings 7 2 COOLING The module has been designed to operate over a wide temperature range 30 to 70º C Allowances should be made for the temperature rise within the control panel enclosure Care should be taken NOT to mount possible heat sources near the module unless adequate ventilation is provided The relative humidity inside the control panel enclos...

Страница 37: ...OPERATING MANUAL ISSUE 5 1 18 06 2007 ADM 37 7 4 FRONT PANEL LAYOUT Deep Sea Electronics Model 5220 O I AUTO i Warming 10s L N 240V 0A 50Hz L L 415V 0kW RUNNING IN AUTO FIG 5 7 5 REAR PANEL LAYOUT FIG 6 CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com ...

Страница 38: ...A 3 Emergency Stop Input 2 5mm AWG 13 Plant Supply Positive Also supplies fuel start outputs Recommended Maximum Fuse 32A 4 Fuel relay Output 2 5mm AWG 13 Plant Supply Positive from pin 3 16 Amp rated 5 Start relay Output 2 5mm AWG 13 Plant Supply Positive from pin 3 16 Amp rated 6 Auxiliary Output relay 1 1 0mm AWG 18 Plant Supply Positive 5 Amp rated 7 Auxiliary Output relay 2 1 0mm AWG 18 Plant...

Страница 39: ...AWG 20 Switch to Negative 16 Functional Earth 2 5mm AWG 13 Connect to a good clean earth point 17 Magnetic pickup Positive 0 5mm AWG 20 Connect to Magnetic Pickup device 18 Magnetic pickup Negative 0 5mm AWG 20 Connect to Magnetic Pickup device 19 Not connected NOTE Ensure magnetic pickup screen is connected to ground at one end only NOTE When the module is configured for CAN operation terminals 1...

Страница 40: ...Not connected NOTE Screened 120Ω impedance cable specified for use with RS485 must be used DSE stock and supply Belden cable 9841 which is a high quality 120Ω impedance cable suitable for RS485 use DSE part number 016 030 8 1 5 PLUG E 8 WAY PIN No DESCRIPTION CABLE SIZE NOTES 27 Mains loading relay 1 0mm AWG 18 Connect to mains contactor coil 28 Mains loading relay 1 0mm AWG 18 Connect to mains co...

Страница 41: ...m AWG 13 Connect to secondary of L3 monitoring CT 42 CT secondary common 2 5mm AWG 13 Connect to secondary of all monitoring CT s 43 Not connected 8 1 8 PLUG H 4 WAY PIN No DESCRIPTION CABLE SIZE NOTES 44 Oil Pressure Input 0 5mm AWG 20 Connect to Oil pressure sender 45 Coolant Temperature Input 0 5mm AWG 20 Connect to Coolant Temperature sender 46 Fuel Level input 0 5mm AWG 20 Connect to Fuel Lev...

Страница 42: ...ector allows connection to PC via the 810 configuration interface Module can then be re configured utilising the 5xxx series configuration software 8 1 10 EXPANSION OUTPUT CONNECTOR The expansion connector allows connection to the 157 relay expansion module or to the 548 LED Remote annunciator module CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com...

Страница 43: ...alibration Manual for options available It is possible to configure the input to be a normally closed signal or a normally open signal 11 Auxiliary input 2 This is a negative switched configurable input see Calibration Manual for options available It is possible to configure the input to be a normally closed signal or a normally open signal 12 Auxiliary input 3 This is a negative switched configur...

Страница 44: ...485 applications 26 Not used Do not connect to this terminal NOTE Screened 120Ω impedance cable specified for use with RS485 must be used DSE stock and supply Belden cable 9841 which is a high quality 120Ω impedance cable suitable for RS485 use DSE part number 016 030 8 2 5 PLUG E 8 WAY PIN No DESCRIPTION 27 Mains loading relay normally closed Volts free contact to terminal 28 28 Mains loading rel...

Страница 45: ...Coolant Temperature sensing input Connect to resistive type coolant temperature sender Refer to connection diagram for details 46 Fuel Level sensing input Connect to resistive type fuel level sender Refer to connection diagram for details 47 Sender Common connection Return feed from sender units refer to connection diagram for details NOTE When the module is configured for CAN operation terminals ...

Страница 46: ...Input Range 15V 277 ph N 20 50Hz 60Hz Accuracy 1 of full scale Average sensing Supported topologies 3 Phase 4wire Single phase 2 wire 3 phase 3 wire 2 Phase 3 wire L1 L2 2 Phase 3 wire L1 L3 CT s Burden 0 5VA Primary rating 1A 6000A user selectable Secondary rating 1A or 5A secondary user selectable Accuracy of measurement 1 of full load rating when using 0 5 or better CTs with 5A secondary windin...

Страница 47: ...ng gasket 2 front of module when module is installed into the control panel WITHOUT being sealed to the panel Product Certification C US European CE approved UL approved C UL CSA approved Russia and other CIS countries approved BS EN 2002 95 EC Restriction of Hazardous Substances RoHS BS EN 2002 96 EC Waste Electrical and Electronic Equipment WEEE Relevant Company Certification BS EN ISO 9001 2000...

Страница 48: ...for the pre set cooling down period then stop The generator should stay in the standby mode If not check that there is not a signal present on the Remote start input and that the mains utility supply is healthy and available 10 8 Initiate an automatic start by supplying the remote start signal or failing the mains utility supply The start sequence will commence and the engine will run up to operat...

Страница 49: ...of attempts to start Check wiring of fuel solenoid Check fuel Check battery supply Check battery supply is present on the Fuel output of the module Check the speed sensing signal is present on the 5320 inputs Refer to engine manual Continuous starting of generator when in AUTO Check that mains utility supply is healthy and check that it s protection fuses are in place and are not blown Check that ...

Страница 50: ...ion description Blank Alternator fitted Yes Poles 4 Magnetic pickup fitted No CAN enabled No AC System 3 phase 4 wire VT Ratio Disabled Mains failure detection Enabled Number of start attempts 3 Enable fast loading feature No Immediate mains dropout Disabled Sleep in STOP mode No All warnings are latched No Input settings Analogue Oil pressure Value Low oil pressure input type VDO 10 bar Trip Retu...

Страница 51: ...rgise Common alarm 3 Energise System in auto mode 4 Energise Close generator 5 De energise Close mains Output settings Expansion A Value 1 Energise System in auto mode 2 Energise Fail to start 3 Energise Generator available 4 Energise Delayed alarms armed 5 Energise Combined under over freq Shutdown 6 Energise Combined under over voltage shutdown 7 Energise Cooling timer in progress 8 Energise Mai...

Страница 52: ... AC 253V AC Under frequency trip 45 0 Hz 48 0 Hz Over frequency trip 55 0 Hz 52 0 Hz Generator settings Voltage frequency Trip Return Under volts trip 184V AC N A Under volts pre alarm 196V AC 207V AC Over volts pre alarm 265V AC 253V AC Over volts trip 276V AC N A Under frequency trip 40 0 Hz N A Under frequency pre alarm 42 0 Hz 45 0 Hz Over frequency pre alarm 55 0 Hz 52 0 Hz Over frequency tri...

Страница 53: ...50 RPM Disabled Overspeed overshoot 0 Disabled Plant battery settings Trip Return Under volts warning 8 0V DC 9 0V DC Over volts warning 33 0V DC 32 0V DC Charge alternator warning 6 0V DC N A Exercise scheduler settings Value Enable exercise scheduler No Comms Value Site identity Genset ID Modem mode No modem Modem init not auto answer E0S7 60S0 0 S0 C1 D3 Modem init auto answer E0S7 60S0 2 S0 C1...

Страница 54: ...lure Instrumentation System Operators Manual 54 Part No 057 014 5320 OPERATING MANUAL ISSUE 5 1 18 06 2007 ADM 13 TYPICAL WIRING DIAGRAM CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com ...

Страница 55: ...ction diagram details how to connect the module when used in a 3 phase 4 wire system 3 phase star connected alternators Changes to this typical wiring diagram for other AC systems are detailed below NOTE The factory default configuration for the 5320 module is for use with the 3 phase 4 wire AC system If another system is to be used the controller must be reconfigured using the 5xxx series configu...

Страница 56: ... ISSUE 5 1 18 06 2007 ADM 14 1 2 1 PHASE 2 WIRE Single phase alternator with neutral conductor 14 1 3 2 PHASE 3 WIRE 2 PHASE CENTRE TAP NEUTRAL The alternator is 2 phase star connected The live phases are separated by 180 CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com ...

Страница 57: ...REMENT UNITS Display Description Display Description Display Description L1 Phase L2 Phase L3 Phase L1 N Phase Neutral L2 N Phase Neutral L3 N Phase Neutral L1 L2 Phase Phase L2 L3 Phase Phase L3 L1 Phase Phase BAR Pressure KPa KPa Oil Pressure Units PSI Pressure V Voltage o F Temperature Hz Frequency A Amperes o C Temperature RPM Speed kW KiloWatts kVA Apparent power KW divided by kVA 14 2 3 LED ...

Страница 58: ... 5 1 18 06 2007 ADM 14 3 5320 IDMT TRIPPING CURVES TYPICAL 5320 Delayed over current protection 1 10 100 1000 10000 100000 1000000 1 2 3 Current as a multiple of the trip point setting tripping curve 36 Tripping time in seconds CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com ...

Страница 59: ...und electrical connection to the sender bodies NOTE If you use PTFE insulating tape on the sender thread when using earth return senders ensure you do not insulate the entire thread as this will prevent the sender body from being earthed via the engine block 14 4 2 INSULATED RETURN SENDERS Connection Name Terminal Number Oil pressure Sender 44 Coolant temperature sender 45 Fuel level sender 46 Sen...

Страница 60: ...easures the distance between the top of the tank and the fuel level Typically they use a ball float In this example the distance between the top of the tank and the level of the fuel is 50 of the height of the tank The fuel level sender will report the tank correctly as being 50 full For a parallel sided tank like this one 50 distance between the top of the tank and the level of the fuel will occu...

Страница 61: ... is available which connects to the configuration socket and enables the 5xxx to use eight additional relays on the 157 relay module providing Volt free contacts for customer connection A maximum of 2 off 157 relay modules can be connected there are identified as A and B and give a total of 16 extra relay outputs Refer to technical data sheet on the 157 relay module for further details 14 6 2 LED ...

Страница 62: ...to the modem Please refer to the comms section of this manual for details of how the system should be configured If RS485 communications is required then it is important to order the correct 5320 module with the RS485 communications board fitted This provides a 3 way terminal block for connection of the RS485 link 14 8 2 PC TO CONTROLLER DIRECT CONNECTION To connect a 5320 to a modem the following...

Страница 63: ...arm system etc NOTE The RS485 system will comprise of one MODBUS master typically a PC and up to 31 MODBUS slaves The 5320 modules are always MODBUS slave devices To ensure correct operation a suitable 120Ω terminal resistor must be fitted to each end of the RS485 connection bus Caution The A and B lines of the 485 network should be terminated at each end with a 120Ω resistor Some RS485 devices PC...

Страница 64: ...ssible to use third party software to monitor and control the 5320 module via this protocol Please refer to Deep Sea Electronics Plc for details 14 8 5 MODBUS The RS485 output uses Modbus communications protocol This uses a master slave technique to communicate Only the Master can initiate a packet transaction called a query When appropriate the slave 5320 Module responds to the query and provides...

Страница 65: ... against ingress of solid objects with a diameter of more than 2 5 mm Tools wires etc with a thickness of more than 2 5 mm are prevented from approach 3 Protection against water falling at any angle up to 60 from the vertical There must be no harmful effect spray water 4 Protected against ingress of solid objects with a diameter of more than 1 mm Tools wires etc with a thickness of more than 1 mm ...

Страница 66: ...ee of protection against windblown dust rain and sleet undamaged by the formation of ice on the enclosure 3R IP32 Provides a degree of protection against rain and sleet undamaged by the formation of ice on the enclosure 4 X IP66 Provides a degree of protection against splashing water windblown dust and rain hose directed water undamaged by the formation of ice on the enclosure Resist corrosion 12 ...