![Deep Sea Electronics Plc DSE5320 Скачать руководство пользователя страница 30](http://html.mh-extra.com/html/deep-sea-electronics-plc/dse5320/dse5320_operating-manual_2463100030.webp)
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
30
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
If the module PIN number has been set, the PIN number request is then shown. The configuration cannot be
viewed or changed until the PIN number is correctly entered.
Enter either the ‘main’ PIN or the application PIN.
If no PIN has been set, then skip to the next section.
NOTE:- The ‘Application Editor’ must be enabled first in order to make it accessible from the
module’s fascia. This is done by setting a PIN (number) for the module’s main front panel editor, using the
5xxx for Windows™ PC configuration software.
Enter pin
The first * is flashing. Press + or – buttons to adjust it to the correct value for the first digit of the
PIN number.
Press
9
when the first digit is correctly entered.
The entered digit will turn back to a * to maintain security.
****
Enter pin
The second * is now flashing. Press + or – buttons to adjust it to the correct value for the second
digit of the PIN number.
Press
9
when the second digit is correctly entered.
The entered digit will turn back to a * to maintain security.
****
Enter pin
The third * is now flashing. Press + or – buttons to adjust it to the correct value for the third digit
of the PIN number.
Press
9
when the third digit is correctly entered.
The entered digit will turn back to a * to maintain security.
****
Enter pin
The fourth * is now flashing. Press + or – buttons to adjust it to the correct value for the fourth
digit of the PIN number.
Press
9
when the fourth digit is correctly entered.
****
NOTE:- When
9
is pressed after editing the final PIN digit, the PIN is checked for validity. If the
number is not correct, the editor is automatically exited. To retry you must re-enter the editor as
described above.
Oil pressure pre-alarm
If the Configuration PIN has been entered successfully (or the PIN number has
not been set in the module) the first configurable parameter is displayed :
2
Bar
30
PSI
200
kPa
NOTE:- To exit the front panel configuration editor at any time, press the Stop/Reset
button.
Ensure you have saved any changes you have made by pressing the
9
button first.
NOTE:- When the editor is visible, it is automatically exited after 5 minutes of inactivity to ensure
security.
NOTE:- If the Application Menu PIN is entered, then only the Application Menu is displayed. If the
Full Configuration PIN is entered, the entire configuration menu is displayed including the Application
Menu.
NOTE:- The PIN number is automatically reset when the editor is exited (manually or automatically)