DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
19
4.6 ELECTRICAL
TRIPS
Electrical trips are latching and stop the Generator but in a controlled manner. On initiation of the electrical trip
condition the module will de-energise the
‘Close Generator’
Output to remove the load from the generator. Once
this has occurred the module will start the Cooling timer and allow the engine to cool off-load before shutting down
the engine. The alarm must be accepted and cleared, and the fault removed to reset the module.
AUXILIARY INPUTS
, if an auxiliary input has been configured as an electrical trip the appropriate message will be
displayed as configured by the user.
Example
Alarm
Electrical trip
Phase rotation
GENERATOR HIGH CURRENT.
If the module detects a generator output current in excess of the pre-set trip a
warning is initiated. If this high current condition continues for an excess period of time, then the alarm is escalated
to either a shutdown or electrical trip condition (depending upon module configuration). For further details of the
high current alarm, please see High Current Shutdown Alarm.
Alarm
Electrical trip
High current