5.8.2.
Recommendations
WARNING
4
Only qualified professionals may carry out electrical
connections, always with the power off.
4
Disconnect the appliance from the mains before any
work on it.
4
The boiler is entirely pre-wired. Do not modify the
connections inside the control panel.
4
Earth the appliance before making any electrical
connections.
WARNING
If the power cable is damaged, it must be replaced by the
manufacturer, its after sales service or persons with
similar qualifications in order to obviate any danger.
Make the electrical connections of the appliance according to:
4
The instructions of the prevailing standards,
4
The instructions on the circuit diagrams provided with the
appliance,
4
The manufacturer’s instructions.
The electrical connections shall comply with standards in force.
The earthing shall comply with local standards.
CAUTION
Separate the sensor cables from the 230 V cables.
In the boiler: use the 2 ducts located on the right hand side
of the boiler for this purpose.
All connections are made to the terminal blocks provided for this
purpose in the boiler connection box.
The connection cables are fed into the boiler by means of two
connection ducts located in the right side panel.
The available output per outlet is 450 W (2 A, with cos
j
= 0.7) and
the inrush current must be lower than 16 A. If the load exceeds either
of these values, the control must be relayed using a contactor that
must not be installed in the control panel under any circumstances.
The sum of the currents from all outlets must not exceed 5 A.
CAUTION
Failure to comply with these instructions could lead to
interference and control unit malfunctioning or even
damage to the electronic circuitry.
5.8.3.
Accessing the connection terminal blocks
Open the access door on the control panel. Remove the front panel