Installer level - #SECONDARY INSTAL.P menu
Parameter
Adjustment range
Description
Factory
setting
Customer
setting
ANTICIP.C
(1)
0.0 to 10.0
Activation and adjustment of the
anticipation time
NO
ROOM INFL.C
(2)
0 to 10
Influence of room sensor C
3
SCREED DRYING
NO, B, C, B+C
Drying the floor
NO
START DRYING TEMP
(3)
20 to 50 °C
Screed drying start temperature
20 °C
STOP DRYING TEMP
(3)
20 to 50 °C
Screed drying stop temperature
20 °C
NB DAYS DRYING
(3)
0 to 99
0
NIGHT
(2)
DEC.
The lower temperature is maintained
(Night mode)
DEC.
STOP
The boiler is stopped (Night mode)
IN 0-10V
OFF
/
TEMPERATURE
/
POWER %
Activating the 0-10 V function
OFF
VMIN/OFF 0-10V
(2)(4)
0 to 10 V
Voltage corresponding to the instruction
set minimum
0.5 V
VMAX 0-10V
(2)(4)
0 to 10 V
Voltage corresponding to the instruction
set maximum
10 V
CONS.MIN 0-10V
(2)(4)
0 to 100 °C / 0 to 100 % Minimum temperature or relative power
setpoint
5 °C / 0%
CONS.MAX 0-10V
(2)(4)
5 to 100 °C / 5 to 100 % Maximum temperature set point or
relative output
100 °C / 80%
BAND WIDTH
(2)
4 to 16 K
Control unit bandwidth for the 3-way
valves.
Option of increasing the bandwidth if the
valves are rapid or of reducing it if they
are slow.
12 K
BOIL/3WV SHIFT
(2)
0 to 16 K
Minimum temperature difference
between the boiler and the valves
4 K
H.PUMP DELAY
(2)
0 to 15 minutes
Timing of the shutdown of the heating
pumps.
The timing of heating pump shutdown
prevents the boiler overheating.
4 minutes
DHW.PUMP DELAY
(2)
2 to 15 minutes
Timing of the shutdown of the domestic
hot water pump.
The timing of the domestic hot water load
pump shutdown prevents the boiler and
the heating circuits overheating (Only if a
load pump is used).
2 minutes
ADAPT
ON
Automatic adaptation of the heating
curves for each circuit with a room sensor
with an influence of >0.
OFF
OFF
The heating curves can only be modified
manually.
(1) The parameter is only displayed if
INSTALLATION
parameter is set to
EXTENDED
(2) The parameter can be set to the heating curve by pressing key
f
(3) The parameter is only displayed if
SCREED DRYING
is other than
OFF
(4) The parameter is only displayed if
IN 0-10V
is set to
ON
.
(5) The parameter is only displayed if
LEG PROTEC
is different from
OFF
(6) The parameter is only displayed if
P.DHW
is set to
PUMP
6. Commissioning
AFC 18 - AFC 24 - AFC 30
116
09/07/2015 - 300026439-07