Installer level - #NETWORK Menu
(1)
Parameter
Adjustment range Description
Factory setting Customer
setting
PARALLEL.CASC
(5)
-10 to 20 °C
Outside temperature triggering all stages
in parallel mode
10 °C
TIMER GENE P.CASC
(3)
0 to 30 min
Minimum duration of post-operation of the
generator pump
0 mn
INTER STAGE TIMER
(3)
1 to 60 min
Time delay for starting up or shutting
down generators.
4 mn
SLAVE NUMBER
(6)
2 to 10
Set the network address of the secondary
generator
2
(1) The menu is displayed only if the
INSTALLATION
parameter is set to
EXTENDED
(2) The parameter is only displayed if
CASCADE
is set to
NO
(3) The parameter is only displayed if
CASCADE
is set to
ON
(4) The parameter is only displayed if
MASTER CONTROLER
is set to
ON
(5) The parameter is only displayed if
FUNCT
is set to
PARALLEL
(6) The parameter is only displayed if
MASTER CONTROLER
is set to
OFF
User level - #SETTING Menu
Parameter Adjustment range Description
Factory setting Customer setting
PERMUT
(1)
AUTO
/ 1 ... 10
This parameter is used to set the master boiler.
4
AUTO
: The master boiler switches automatically
every 7 days
4
1 ... 10: The master boiler is always the one
defined by this value
AUTO
(1) The parameter is only displayed if
CASCADE
is on
ON
and
MASTER CONTROLER
on
ON
n
Connecting appliances in cascade
It is possible, in a cascade configuration, to enlist generators and/or
VM iSystem as slaves. Proceed as follows:
1. Set parameter
CASCADE
to
ON
.
2. Select
SYSTEM NETWORK
and press the rotary button to go to
the specific menu.
3. To add a slave appliance to the network, select
ADD SLAVE
.
1
1
2
2
r
c
STD
(
'
t
v
0
2
4
6
8
10
12
14
16
18
22
24
20
p
b
AUTO
x c
r
j
L
g
m
CASCADE
MASTER CONTROLER
SYSTEM NETWORK
FUNCT
INTER STAGE TIMER
ON
ON
TRADITIONAL
4'
a
C002409-C-04
1
1
2
2
r
c
STD
(
'
t
v
0
2
4
6
8
10
12
14
16
18
22
24
20
p
b
AUTO
x c
r
j
L
g
m
NB.NETWORK ELEMENTS
ADD SLAVE
ERASE NETWORK
4
a
C002410-C-04
AFC 18 - AFC 24 - AFC 30
6. Commissioning
09/07/2015 - 300026439-07
123