![DeDietrich IX 145-110 Скачать руководство пользователя страница 68](http://html1.mh-extra.com/html/dedietrich/ix-145-110/ix-145-110_installation-and-service-manual_2462473068.webp)
Unit
CO
2
Authorised CO
2
%
9.8
9.1 - 9.5
%
9.9
9.2 - 9.6
%
10.0
9.3 - 9.7
%
10.1
9.4 - 9.8
%
10.2
9.5 - 9.9
%
10.3
9.6 - 10.0
%
10.4
9.7 - 10.1
%
10.5
9.8 - 10.2
(1) The CO
2
value is valid with the front panel mounted. If the front panel is removed (open chamber), the value readout is lower by 0.2 %.
(2) Nominal value.
Important
The amount of CO
2
permitted at minimum power depends on the
amount of CO
2
measured at maximum power. In accordance with
the new standard EN15502 for gas boilers, the settings ranges for
CO
2
at minimum power are indicated for each CO
2
value
measured at maximum power.
8.4.6
Adapting the boiler to a different type of gas
Caution
Only a fully trained, qualified professional may carry out the
following operations.
The boiler is pre-set in the factory to run on natural gas H (G20).
Conversion kits are available for other types of gas G25 and G31.
1. Close the mains gas valve.
2. Remove the pipe connecting the Venturi to the gas valve.
Tab.47 Connection pipe
Reference
Model
A
IX 145–50
B
IX 145–70
IX 145–90
IX 145–110
3. Remove the Venturi unit.
4. Replace the original Venturi unit with the Venturi unit provided in the
conversion kit.
Fig.68
MW
-3
0
0
0
0
4
8
-0
2
A
2
2
B
Fig.69
Removing the Venturi unit
MW
-3
0
0
0
0
4
9
-0
2
A
B
3
3
8 Commissioning
68
IX
7702703 - v04 - 05092019