![DeDietrich IX 145-110 Скачать руководство пользователя страница 52](http://html1.mh-extra.com/html/dedietrich/ix-145-110/ix-145-110_installation-and-service-manual_2462473052.webp)
Important
For B
23p
configurations, the lengths given in the tables are valid
for horizontal pipes with a maximum length of 1 metre. For each
additional metre of horizontal pipe, subtract 1.2 m from the vertical
length L
max
.
Tab.28 Flue system connection type B
23p
for IX 145–50 and IX 145–70
Arrangement
Configuration
Unit
IX 145–50
IX 145–50
IX 145–70
IX 145–70
mm
Ø 80
Ø 110
Ø 80
Ø 110
L3<2m + 2 elbows
(L1 + L2) rigid
m
20
56
8
56
L3<2m + 2 elbows
(L1 + L2) flexible
m
15
56
6
38
L3<5m + 2 elbows
(L1 + L2) rigid
m
–
56
–
56
L3<5m + 2 elbows
(L1 + L2) flexible
m
–
56
–
38
Tab.29 Flue system connection type B
23p
for IX 145–90 and IX 145–110
Arrangement
Configuration
Unit
IX 145–90
IX 145–90
IX 145–110
IX 145–
110
IX 145–
110
mm
Ø 110
Ø 125
Ø 110
Ø 125
Ø 160
L3<2m + 2 elbows
(L1 + L2) rigid
m
20
56
56
56
–
L3<2m + 2 elbows
(L1 + L2) flexible
m
–
21
15
–
–
L3<5m + 2 elbows
(L1 + L2) rigid
m
24
56
–
43
56
L3<5m + 2 elbows
(L1 + L2) flexible
m
13
–
–
–
–
C
13
Configuration
Important
Pipes subject to technical evaluation 14 08–1289.
Fig.54
Rigid flue system B
23p
MW
-3
0
0
0
0
3
5
-2
L1
L2
L3
Fig.55
Through-roof flue system B
23p
MW
-3
0
0
0
0
3
6
-1
L1
L2
L3
7 Installation
52
IX
7702703 - v04 - 05092019
Содержание IX 145-110