6.1.2
Electrical connection
Fig.31
1 direct c 1 domestic hot water tank
1
2
3
4
A
ux 1-2 230 V
TA
TS
L
N
T1
T2
L
L
N
N
S1
S2
L
N
MW-3000114-08
167
21
33
38
34
26
2
1 2 3
X40
2 Direct heating circuit pump
21 Outside temperature sensor
26 DHW booster pump
33 Domestic hot water temperature sensor
34 Modulating boiler pump (primary pump)
38 Remote control
167 Boiler control panel
Important
Relay the pumps if the current exceeds 1 A max per output.
6.1.3
Configuration
1. Go to the installer parameters.
2. Set/check the following parameters on the boiler:
Tab.15 Settings for the 1 direct zone + 1 domestic hot water tank
Parameter number
Parameter
Adjustment/check required
5710
Temps / mode CH1
On
5715
Temps / mode CH2
Off
5721
Temps / mode CH3
Off
5730
Hot water sensor
Hot water sensor B3
5731
HW controlling element
Charging pump
5890
Relay output QX1
heating pump CH1 Q2
5891
Relay output QX2
Boiler pump Q1
5892
Relay output QX3
Hot water ctrl elem Q3
5931
Sensor input BX2
None
6 Connecting diagrams and configuration
7702703 - v04 - 05092019
IX
35