R
Pool heating cut-off control
When the parameter
I.TEL:
is on
0/1 B
, the
swimming pool is no longer heated when the
contact is open (factory setting), only the
antifreeze continues to be active.
The contact direction can still be adjusted by the
parameter
CT.TEL
.
T
Connect the primary swimming pool pump.
Y
Do not connect anything to the terminal block.
Settings to be made for this type of installation
Parameters
Access
Settings to be made
See chapter
INSTALLATION
"Installer" level
#SYSTEM
menu
EXTENDED
¼
CIRC. B:
"Installer" level
#SYSTEM
menu
SWIM.P.
¼
"Setting the parameters specific
If
I.TEL:
is used
I.TEL:
"Installer" level
#SYSTEM
menu
0/1 B
MAX. CIRC. B
"Installer" level
#SECONDARY LIMITS
menu
Set the value of
MAX.CIRC.B
to
the temperature corresponding
to the needs of the exchanger
¼
""Professional" settings", page
n
Controlling the pool circuit
The control system can be used to manage a swimming pool circuit
in both cases:
Case 1: The control system regulates the primary circuit (boiler/
exchanger) and the secondary circuit (exchanger/pool).
4
Connect the primary circuit pump (boiler/exchanger) to the
M
B
outlet on the connection terminal block. The temperature
MAX.CIRC.B
is then guaranteed during comfort periods on
programme
B
in summer and winter alike.
4
Connect the swimming pool sensor (package AD212) to the
S
DEP B
inlet on the connection terminal block.
4
Set the set point of the pool sensor using key
C
in the range 5 -
39°C.
Case 2: The pool has already a regulation system that is to be
kept. The control system only regulates the primary circuit
(boiler/exchanger).
4
Connect the primary circuit pump (boiler/exchanger) to the
M
B
outlet on the connection terminal block.
The temperature
MAX.CIRC.B
is then guaranteed during comfort
periods on programme
B
in summer and winter alike.
The swimming pool can also be connected to circuit
C
by
adding the AD249 option:
4
Make the connection to the terminal blocks marked
C
.
4
Set the parameters for circuit
C
.
MCA 15 - MCA 25 MCA 25/28 MI
4. Installation
29/04/2010 - 300022146-001-B
47
Содержание Innovens MCA 15
Страница 7: ...29 04 2010 300022146 001 B 5...
Страница 141: ...MCA 15 MCA 25 MCA 25 28 MI 9 Spare parts 29 04 2010 300022146 001 B 139...
Страница 142: ...9 Spare parts MCA 15 MCA 25 MCA 25 28 MI 140 29 04 2010 300022146 001 B...
Страница 143: ......