"User" level - #SETTING menu
Parameter
Adjustment
range
Description
Factory setting
Customer
setting
SUM/WIN
15 to 30 °C
Used to set the outside temperature above
which heating will be shut down.
4
The heating pumps are shut down.
4
The burner will only start for domestic hot
water needs.
4
The letter
E
and the symbol
p
are
displayed.
22 °C
NO
Heating is never shut down automatically
CALIBR. OUT
Outside sensor calibration: Used to correct the
outside temperature
Outside
temperature
CALIBR. ROOM A
(1)
Calibration of the room sensor on circuit A: Is
used to set a room offset
Make this setting 2 hours after switching on,
when the room temperature has stabilised
Room temperature
of circuit A
OFFSET ROOM A
(2)
-5.0 to +5.0 °C
Room offset on circuit A: Is used to set a room
offset
Make this setting 2 hours after switching on,
when the room temperature has stabilised
0.0
ANTIFR. ROOM A
0.5 to 20 °C
Room temperature antifreeze activation on
circuit A
6 °C
CALIBR. ROOM B
(1)(3)
Calibration of the room sensor on circuit B: Is
used to set a room offset
Make this setting 2 hours after switching on,
when the room temperature has stabilised
Room temperature
of circuit B
OFFSET ROOM B
(2)(3)
-5.0 to +5.0 °C
Room offset on circuit B: Is used to set a room
offset
Make this setting 2 hours after switching on,
when the room temperature has stabilised
0.0
ANTIFR. ROOM B
(3)
0.5 to 20 °C
Room temperature at which the antifreeze
mode is activated on circuit B
6 °C
CALIBR. ROOM C
(1)(3)
Calibration of the room sensor on circuit C: Is
used to set a room offset
Make this setting 2 hours after switching on,
when the room temperature has stabilised
Room temperature
of circuit C
OFFSET ROOM C
(2)(3)
-5.0 to +5.0 °C
Room offset on circuit C: Is used to set a room
offset
Make this setting 2 hours after switching on,
when the room temperature has stabilised
0.0
ANTIFR. ROOM C
(3)
0.5 to 20 °C
Room temperature antifreeze activation on
circuit C
6 °C
(1) The parameter is only displayed if a room sensor is connected to the circuit concerned
(2) The parameter is only displayed if no room sensors are connected to the circuit concerned
(3) The parameter is only displayed if the circuit concerned is actually connected
MCA 15 - MCA 25 MCA 25/28 MI
5. Start-up
29/04/2010 - 300022146-001-B
81
Содержание Innovens MCA 15
Страница 7: ...29 04 2010 300022146 001 B 5...
Страница 141: ...MCA 15 MCA 25 MCA 25 28 MI 9 Spare parts 29 04 2010 300022146 001 B 139...
Страница 142: ...9 Spare parts MCA 15 MCA 25 MCA 25 28 MI 140 29 04 2010 300022146 001 B...
Страница 143: ......