"Installer" level - #SECONDARY LIMITS menu
Parameter
Adjustment range Description
Factory setting
MAX.CIRC.A
20 to 95 °C
Maximum temperature (Circuit A)
See comments below
75 °C
MAX.CIRC.B
20 to 95 °C
Maximum temperature (Circuit B)
See comments below
50 °C
MAX.CIRC.C
20 to 95 °C
Maximum temperature (Circuit C)
See comments below
50 °C
OUT.ANTIFREEZE OFF
, -8 to +10 °C
Outside temperature at which the installation's antifreeze protection
is activated.
Below this temperature the pumps are permanently on and the
minimum temperatures for each circuit are respected.
When
NIGHT : STOP
is set, the reduced temperature is maintained
in each circuit (
#SECONDARY INSTAL.P
menu).
OFF
: Antifreeze protection is not activated
+3 °C
HCZP D A
(1)(2)
OFF
, 20 to 90 °C
Curve base temperature in Daytime mode (Circuit A)
OFF
HCZP N A
(1)(2)
OFF
, 20 to 90 °C
Curve base temperature in Nighttime mode (Circuit A)
OFF
HCZP D B
(1)(2)
OFF
, 20 to 90 °C
Curve base temperature in Daytime mode (Circuit B)
OFF
HCZP N B
(1)(2)
OFF
, 20 to 90 °C
Curve base temperature in Nighttime mode (Circuit B)
OFF
HCZP D C
(1)(2)
OFF
, 20 to 90 °C
Curve base temperature in Daytime mode (Circuit C)
OFF
HCZP N C
(1)(2)
OFF
, 20 to 90 °C
Curve base temperature in Nighttime mode (Circuit C)
OFF
(1) The parameter is only displayed if
INSTALLATION
parameter is set to
EXTENDED
(2) The parameter can be set to the heating curve by pressing key
f
.
"Installer" level - #PRIMARY INSTAL.P menu
Parameter
Adjustment range Description
Factory setting Customer setting
BURN.MIN.RUN
(1)(2)
0 to 180 seconds
Setting the burner minimum operation time
(In heating mode)
30 seconds
TIMER GENE P.
(2)
1 to 30 minutes
Maximum post-operation duration of the
generator pump
4 minutes
IN.BL
(2)
STOP HEAT
Configuration of the PCU BL inlet
If the contact is open, the heating is off. If the
parameter
P.DHW
is set to VI, DHW
production nevertheless remains functional.
Automatic restart when the contact closes.
TOTAL STOP
TOTAL STOP
Configuration of the PCU BL inlet
If the contact is open, heating and DHW
production are off. Automatic restart when
the contact closes.
SAFETY MODE
Configuration of the PCU BL inlet
If the contact is open, the boiler goes into
safety lockout. The boiler needs to be reset
to restart.
(1) The parameter is only displayed if
INSTALLATION
parameter is set to
EXTENDED
(2) The parameter can be set to the heating curve by pressing key
f
MCA 15 - MCA 25 MCA 25/28 MI
5. Start-up
29/04/2010 - 300022146-001-B
83