Settings to be made for this type of installation
Parameters
Access
Settings to be made See chapter
INSTALLATION
"Installer" level
#SYSTEM
menu
EXTENDED
¼
"Displaying the parameters in extended mode", page
I.SYST
(1)
"Installer" level
#SYSTEM
menu
ST.TANK+DHW
¼
"Setting the parameters specific to the installation",
O.DHW:
(1)
"Installer" level
#SYSTEM
menu
PUMP
(1) The parameter is only displayed if
INSTALLATION
parameter is set to
EXTENDED
The DHW tank is loaded from the storage tank. If, during
DHW loading, the temperature of the storage tank falls
below the primary DHW set point (parameter
PRIM.TEMP.DHW), the boiler maintains the latter at
temperature to guarantee the loading of the DHW tank
The heating zone is maintained at the set temperature
calculated according to the outside temperature. The zone
is reheated when the heating buffer temperature sensor
falls -6°C below the calculated set temperature. Reheating
in the heating zone stops when the heating buffer
temperature rises above the calculated set temperature.
4.10.10. Pool connection
C002298-i
1
3
5
2
6
On/off
OT
BL
RL
Tout
Tdhw
TS +
B
A
B
0-10V
S AMB C
4 3 2 1
2 1
+ -
S AMB B
2 1
S AMB A
2 1
S SYST + TA -
S ECS
S EXT
S DEP C
2 1
2 1
2 1
2 1
2 1
S DEP B
2 1
SCU
PCU
4
A
Connect the secondary swimming pool pump.
Z
Connect the swimming pool sensor.
E
Plate heat exchanger.
4. Installation
MCA 15 - MCA 25 MCA 25/28 MI
46
29/04/2010 - 300022146-001-B