10. Wiring diagram
Address dipswitch
Dipswitch 1…3
Bus address setting
Dipswitch 4
Speed setting; “off” 0,8 rpm (standard setting), “on” 0,4 rpm
Dipswitch 5
PS100-mode. When set to “on”, the KL300 is PS100 compatible;
- maximum current is reduced to 2A
- maximum pulling force is reduced to 160 kg
Offset Device address = 0 (Default value register 0x3A8:0X3A9)
Address 1
Address 2
Address 3
Address 4
Address 5
Address 6
Address 7
Address 8
Modbus RTU or CAN-LOCAL bus selection dipswitch
In order to select the correct bus, set the dipswitches in the correct position. For CAN-LOCAL bus switches 1 & 2
must be set to “on”, 3 & 4 is set to “off”. For Modbus RTU switches 1 & 2 must be set to “off”, 3 & 4 is set to
“on”. See picture for reference.
Termination resistor dipswitch
When a bus system is connected, the use of a termination resistor is necessary. This termination resistor is
activated by switching the dipswitch to “1”. This is only required at the last KL300 in the network.
Shield
Shield
GND
H/A L/B
GND
GND
24 VDC
24 VDC
PE
PE
Alar
m
Alar
m
0...10VDC
0...10 VDC control signal
Alarm contact (max. 1A @ 24 VDC/AC
24 VDC Supply voltage ±10%
Modbus RTU (A&B) or CAN-LOCAL (H&L) out
Modbus RTU (A&B) or CAN-LOCAL (H&L) in
Alarm contact (max. 1A @ 24 VDC/AC)
24 VDC Supply voltage ±
Wiring diagram Modbus RTU and/or CAN-LOCAL bus
Wiring diagram 0 ... 10 VDC control
Shield
H/A L/B