6. Settings
Programming endpositions for Modbus RTU / CAN-LOCAL
Note: for status messages and troubleshooting read-in problems please check section 8.
1. Press button “OK” for 5 seconds.. The green LED “I” will flash. The first position can now be set.
2. Let the KL300 run to the maximum position by pressing the button “I” or “II”. The KL300 will run
automatically if button “OK” is pressed shortly (pulse) simultaneously with button “I” or “II”. To stop the
KL300 again, button “I” or “II” must be pressed shortly.
Caution
The KL300 will not stop in automatic mode. If a maximum position is overrun, damage may occur to the
system and/or construction.
3. Select the “OK” button to set the first position in the KL300 memory. When this position is correctly set,
the LED “OK” will flash and both LED’s “I” and “II” are off.
4. Press button “OK” for 5 seconds
5. Let the KL300 run to the minimum position by pressing the button “I” or “II”. The KL300 will run
automatically if button “OK” is pressed shortly (pulse) simultaneously with button “I” or “II”. To stop the
KL300 again, button “I” or “II” must be pressed shortly.
Caution
The KL300 will not stop in automatic mode. If a maximum position is overrun, damage may occur to the
system and/or construction.
6. Select the “OK” button to set the second position in the KL300 memory. When this position is correctly set,
the LED “OK” is on together with the LED of the last selected position “I” or “II”.
7. Both end positions of the KL300 are set. The KL300 will automatically run to the position that is set at the
climate controller.
Previous steps are shown in the table on the next page.
Tip!
Verify if the KL300 is set at the correct positions before automatic operation.