6. Settings
Led indication for Modbus RTU/ CAN-LOCAL
Step Action
OK
I
II
Description
Endposition have not been
programmed
1
Press “OK” button for 5
sec
(OFF)
(OFF)
ready to set 1
th
endposition
2
Press “I” or “II” to adjust
the KL300 to the correct
position
3
Press “OK” to set the 1th
position
(ON)
(OFF)
(OFF)
Programming mode: waiting
on correct control signal
4
Press button “OK”for 5
sec.
(OFF)
(OFF)
Ready to set 2
nd
endposition
6
Press “I” or “II” to adjust
the KL300 to the correct
position
7
Press “OK” to set the 2nd
position
(ON)
(ON)
(OFF)
Programming ready, KL300 is
in endposition direction “I”
or
(ON)
(OFF)
(ON)
Programming ready, KL300 is
in endposition direction “II”
7
Set climate controller in
automatic mode
(ON)
(OFF)
(OFF)
Operating mode: KL300 is
between endpositions
(ON)
(OFF)
Operating mode: KL300
moves in direction “I”
(ON)
(OFF)
Operating mode: KL300
moves in direction “II”
(ON)
(ON)
(OFF)
Operating mode: KL300 is @
endposition “I”
(ON)
(OFF)
(ON)
Operating mode: KL300 is @
endposition “II”