background image

14

If above solutions don’t work, please contact your installer or Davey service agent with detailed information 

and your model number. Don’t try to repair it yourself.

NOTE: 

If the following conditions happen, please stop the machine immediately, and cut off the power

 

supply 

immediately, then contact your dealer or Davey: 
1. Inaccurate switch action.
2. The fuse is frequently broken or leakage circuit breaker jumped.

Guidance for flammable gas maintenance.

Please refer to the technical service manual for more information on 

service and maintenance.

Any maintenance on the refrigeration circuit including handling, installation,
cleaning and servicing and disposal must be carried out by licensed personnel and in 

compliance with national gas regulations

1. Detection of flammable refrigerants

  Under no circumstances should potential sources of ignition be used in the searching for or detection of 

refrigerant leaks. A halide torch (or any other detector using a naked flame) should not be used. 

2. Leak detection method

  Electronic leak detectors may be used to detect refrigerant leaks but, in the case of flammable 

refrigerants, the sensitivity may not be adequate, or may need re-calibration. 

  Any calibration of detection equipment should be done in a refrigerant free area.
  Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. 
  Leak detection equipment should be set at a percentage of the LFL of the refrigerant and should be 

calibrated to the refrigerant used, and the appropriate percentage of gas (25% maximum) is confirmed.

  Leak detection fluids are suitable for use with most refrigerants but the use r of detergents containing 

chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipework. 

  If a leak is suspected, all naked flames should be removed or extinguished. 
  If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from 

the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. For 

appliances containing flammable refrigerants, oxygen free nitrogen (OFN) should be purged through the 

system both before and during the brazing process.

3. Refrigerant removal and evacuation

  When breaking into the refrigerant circuit to make repairs, or for any other purpose, conventional 

procedures should be followed. For flammable refrigerants, it is important that best practice is followed 

since flammability is a consideration. 

  The following procedure should be adhered to;

  Remove refrigerant

  Purge the circuit with inert gas

 Evacuate

  Purge again with inert gas

  Open the circuit by cutting or brazing
  The refrigerant charge should be recovered into the correct recovery cyclinders. For flammable 

refrigerants, the system should be flushed with Oxygen Free Nitrogen (OFN) to render the unit safe. This 

process may need to be repeated several times. Compressed air or oxygen cannot be used for purging 

refrigerant systems.

  For appliance containing flammable refrigerants, flushing should be achieved by breaking the vacuum in the 

system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, 

and finally fulling down to a vacuum. This process should be repeated until no refrigerant is within the 

system. When the final OFN charge is used, the system should be vented down to atmospheric pressure to 

enable work to take place. This operation is vital if brazing operations on pipework are to take place.

  Ensure that the outlet for the vacuum pump is not close to any ignition sources and that ventilation is available.

Содержание DHP90

Страница 1: ...Please pass on these instructions to the operator of this equipment Pool Heat Pump Installation and Operating Instructions...

Страница 2: ...ANCE 7 4 1 Installation reminder 7 4 2 Wiring 9 4 3 Electric wiring diagram 9 4 4 References for protecting devices and cable specification 9 5 OPERATION GUIDANCE 10 5 1 Key function 10 5 2 Operation...

Страница 3: ...appliance or an operating electric heater Do not pierce or burn Be aware that refrigerants may not contain an odour R32 Gas INSTALLATION REMINDERS The installation of any pipework should be kept to a...

Страница 4: ...r outage happens during operation the heat pump will start when the power is restored c Please switch off the main power supply in lightening and storm weather to prevent from damage caused by lightni...

Страница 5: ...ortant to ensure that the flow rate in set to the advised water flow rate in section 3 6 and that the pressure does not exceed 500kPa In accordance with AS NZS 60335 2 40 we are obligated to inform yo...

Страница 6: ...0 19 1 38 0 26 1 80 0 33 2 50 0 38 2 90 0 49 3 80 0 65 4 84 Input power at 50 speed kW 0 51 0 7 0 95 1 1 1 44 1 84 Rated input current A 0 83 5 98 1 13 7 83 1 44 10 90 1 66 12 7 2 15 16 53 0 95 7 01...

Страница 7: ...his heat through its heat exchanger to the pool water Your Davey heat pump should be installed in a well ventilated area WARNING Improper installation adjustment service maintenance or use can cause f...

Страница 8: ...fastened the bracket must be strong enough and antirust treated 2 Please ensure 50cm of clearance around each side of the Davey heat pump or the efficiency of the heat pump will be reduced 3 Although...

Страница 9: ...full disconnection of the power supply must be incorporated in the fixed wiring in accordance with the wiring rules 4 3 Electric wiring diagram a For power supply 230V 50Hz Distribution Box Power Sup...

Страница 10: ...ark when it s locked 5 2 Operation Instruction a Screen Lock 1 Press for 3 seconds to lock or unlock the screen 2 Automatic Lock Period 30 seconds if no operation b Power On Press for 3 seconds to unl...

Страница 11: ...ss to exit status check mode SYMBOL CONTENT UNIT C0 Inlet water temp C C1 Outlet water temp C C2 Ambient temp C C3 Exhaust temp C C4 Outer coil pipe temp C C5 Gas return temp C C6 Inner coil pipe temp...

Страница 12: ...to occur to the Davey heat pump a Turn off the circuit breaker or isolation switch b Drain the Davey heat pump Loosen all water connections c Rinse the interior of the heat exchanger cylinder with a...

Страница 13: ...avoided The area around the workspace should be sectioned off Ensure that all conditions within the area have been made safe by control of flammable material 3 Always check the work area with an appr...

Страница 14: ...chlorine may react with the refrigerant and corrode the copper pipework If a leak is suspected all naked flames should be removed or extinguished If a leakage of refrigerant is found which requires b...

Страница 15: ...outlet water Insufficient water flow protection 4 Eb Ambient temperature too high or too low protection 5 Ed Anti freezing reminder No Display Failure Code Description 1 E1 High pressure protection 2...

Страница 16: ...mperature difference then either restart the heat pump or go back into standby The default setting is P2 To change these parameters please contact your nearest Davey dealer verter heat pump solution I...

Страница 17: ...V 50Hz Customer prepare Power Supply 230V 50Hz Earthing Water pump 230V voltage 500W capacity Breaker fuse Customer prepare Breaker fuse Customer prepare Contactor Powercord 17 Customer remote control...

Страница 18: ...18...

Страница 19: ...nt Registration Register by e mail or third party application Android iOS a E mail registration Android please download from iPhone please download from 1 APP Download 2 Account registration 1 Registe...

Страница 20: ...20 Please set family name and choose location of device Create Family b Register through third party application...

Страница 21: ...21 APP Pairing a With Bluetooth 1 Please confirm that you re connected to Wi Fi and your Bluetooth is on 2 Click Add Device and then follow the instructions to pair device...

Страница 22: ...d release After hearing Beep enter Wi Fi password in app During connection will flash Once the app connects to Wi Fi successfully will display b With Wi Fi 1 Please make sure you are connected to Wi F...

Страница 23: ...r On Off Setting temperature Select Boost Silence Mode 2 For heat pump with Heating Cooling function Compressor speed Query C F switch Setting temperature Select Boost Silence Mode Compressor speed In...

Страница 24: ...ather forecast is just for reference 2 App is subject to updates without notice After pairing if your family members also want to control the device please let your family members register InverGo fir...

Страница 25: ...tor DHP3503 1 14 403771 Sensors full set 1 16 16294 R32 Compressor DHP130 1 16 16296 R32 Compressor DHP170 210 1 16 16304 R32 Compressor DHP280 1 16 16305 R32 Compressor DHP3503 1 16 16292 R32 Compres...

Страница 26: ...26 NOTES...

Страница 27: ...27...

Страница 28: ...their product knowledge and reasonable judgement and will be accepted if a relevant defect is found the warranty claim is made during the relevant warranty period and none of the excluded conditions...

Отзывы: