11
e. Wi-Fi
When the screen is on, press
for 3 seconds, after flashing, enter Wi-Fi connection. Connect Wi-Fi
on mobile phone and input password, and then control equipment via Wi-Fi. When APP connects Wi-Fi
successfully lights on.
f. Defrosting
1) Automatic defrosting: When machine is auto defrosting,
will flash, and return to previous working
mode when it finishes.
2) Manual Defrosting: To enter forced defrosting mode, the compressor must be on for more than 10
minutes. In heating mode, hold
and
on touch controller simultaneously for 5 seconds to start
forced defrosting,
is flashing and defrost starts,
stop flashing and defrosting stops.
(Remarks: the interval between manual defrosting should be more than 30 minutes).
g. Heat Pump Status Checking
Make sure the heat pump is running.
Press
for 5 seconds until you hear a beep, it will enter into running status check, the display
alternately shows the status point C0 and its corresponding value.
Use up and down arrows to show the other values.
Press
to exit status check mode.
SYMBOL
CONTENT
UNIT
C0
Inlet water temp
°C
C1
Outlet water temp
°C
C2
Ambient temp
°C
C3
Exhaust temp
°C
C4
Outer coil pipe temp
°C
C5
Gas return temp
°C
C6
Inner coil pipe temp
°C
C9
Radiator temp
°C
C10
Electronic expansion valve opening
P
C11
DC fan speed
r/min
6. TESTING
6.1 Inspect heat pump before use
a. Ensure the ventilation is adequate and there are no obstructions.
b. Ensure your Davey heat pump is not close to any corrosive substances.
c. Verify that the electrical wiring has been completed as per instructions.
6.2 Leakage detection notice and method
a. Keep away from any sources of ignition. A halide torch
(or any other detector using a naked flame) shall not be used.
b. Leakage detection fluids can be applied with most refrigerants but the use of detergents containing
chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe.
c. If a gas leak occurs, cease operation and contact a Davey service centre.
6.3 Trial
a. Your water circulation pump must be running before your Davey heat pump starts and needs to continue
running until after your heat pump stops. This will avoid damage to your heat pump.
R32 Gas