4. Refrigerant charging procedure

  In addition to conventional charging procedures, the following requirements shall be followed;
  Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses 

or lines should be as short as possible to minimise the amount of refrigerant contained in them. 

  Cylinders should be kept upright.
  Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
  Label the system when changing is complete (if not already).
  Extreme care should be taken to not overfill the refrigeration system. 
  Prior to recharging the system, it should be pressure tested with the appropriate purging gas. The system 

shall be leak tested on completion of changing but prior to commissioning. A follow up leak test should be 

carried out prior to leaving the site.

Protection and Failure Codes

No.

Display

Protection Code Description

1

E3

No water protection

2

E5

Power supply exceeds operation range

3

E6

Excessive temp difference between inlet and outlet water 

(Insufficient water flow protection)

4

Eb

Ambient temperature too high or too low protection

5

Ed

Anti-freezing reminder

No.

Display

Failure Code Description

1

E1

High pressure protection

2

E2

Low pressure protection

3

E4

3 phase sequence protection (three phase only)

4

E7

Water outlet temp too high or too low protection

5

E8

High exhaust temp protection

6

EA

Evaporator overheat protection (only at cooling mode)

7

P0

Controller communication failure

8

P1

Water inlet temp sensor failure

9

P2

Water outlet temp sensor failure

10

P3

Gas exhaust temp sensor failure

11

P4

Evaporator coil pipe temp sensor failure

12

P5

Gas return temp sensor failure

13

P6

Cooling coil pipe temp sensor failure

14

P7

Ambient temp sensor failure

15

P8

Cooling plate sensor failure

16

P9

Current sensor failure

17

PA

Restart memory failure

18

F1

Compressor drive module failure

19

F2

PFC module failure

20

F3

Compressor start failure

21

F4

Compressor running failure

22

F5

Inverter board over current protection

23

F6

Inverter board overheat protection

24

F7

Current protection

25

F8

Cooling plate overheat protection

26

F9

Fan motor failure

27

Fb

Power filter plate No-power protection

28

FA

PFC module over current protection

Содержание DHP90

Страница 1: ...Please pass on these instructions to the operator of this equipment Pool Heat Pump Installation and Operating Instructions...

Страница 2: ...ANCE 7 4 1 Installation reminder 7 4 2 Wiring 9 4 3 Electric wiring diagram 9 4 4 References for protecting devices and cable specification 9 5 OPERATION GUIDANCE 10 5 1 Key function 10 5 2 Operation...

Страница 3: ...appliance or an operating electric heater Do not pierce or burn Be aware that refrigerants may not contain an odour R32 Gas INSTALLATION REMINDERS The installation of any pipework should be kept to a...

Страница 4: ...r outage happens during operation the heat pump will start when the power is restored c Please switch off the main power supply in lightening and storm weather to prevent from damage caused by lightni...

Страница 5: ...ortant to ensure that the flow rate in set to the advised water flow rate in section 3 6 and that the pressure does not exceed 500kPa In accordance with AS NZS 60335 2 40 we are obligated to inform yo...

Страница 6: ...0 19 1 38 0 26 1 80 0 33 2 50 0 38 2 90 0 49 3 80 0 65 4 84 Input power at 50 speed kW 0 51 0 7 0 95 1 1 1 44 1 84 Rated input current A 0 83 5 98 1 13 7 83 1 44 10 90 1 66 12 7 2 15 16 53 0 95 7 01...

Страница 7: ...his heat through its heat exchanger to the pool water Your Davey heat pump should be installed in a well ventilated area WARNING Improper installation adjustment service maintenance or use can cause f...

Страница 8: ...fastened the bracket must be strong enough and antirust treated 2 Please ensure 50cm of clearance around each side of the Davey heat pump or the efficiency of the heat pump will be reduced 3 Although...

Страница 9: ...full disconnection of the power supply must be incorporated in the fixed wiring in accordance with the wiring rules 4 3 Electric wiring diagram a For power supply 230V 50Hz Distribution Box Power Sup...

Страница 10: ...ark when it s locked 5 2 Operation Instruction a Screen Lock 1 Press for 3 seconds to lock or unlock the screen 2 Automatic Lock Period 30 seconds if no operation b Power On Press for 3 seconds to unl...

Страница 11: ...ss to exit status check mode SYMBOL CONTENT UNIT C0 Inlet water temp C C1 Outlet water temp C C2 Ambient temp C C3 Exhaust temp C C4 Outer coil pipe temp C C5 Gas return temp C C6 Inner coil pipe temp...

Страница 12: ...to occur to the Davey heat pump a Turn off the circuit breaker or isolation switch b Drain the Davey heat pump Loosen all water connections c Rinse the interior of the heat exchanger cylinder with a...

Страница 13: ...avoided The area around the workspace should be sectioned off Ensure that all conditions within the area have been made safe by control of flammable material 3 Always check the work area with an appr...

Страница 14: ...chlorine may react with the refrigerant and corrode the copper pipework If a leak is suspected all naked flames should be removed or extinguished If a leakage of refrigerant is found which requires b...

Страница 15: ...outlet water Insufficient water flow protection 4 Eb Ambient temperature too high or too low protection 5 Ed Anti freezing reminder No Display Failure Code Description 1 E1 High pressure protection 2...

Страница 16: ...mperature difference then either restart the heat pump or go back into standby The default setting is P2 To change these parameters please contact your nearest Davey dealer verter heat pump solution I...

Страница 17: ...V 50Hz Customer prepare Power Supply 230V 50Hz Earthing Water pump 230V voltage 500W capacity Breaker fuse Customer prepare Breaker fuse Customer prepare Contactor Powercord 17 Customer remote control...

Страница 18: ...18...

Страница 19: ...nt Registration Register by e mail or third party application Android iOS a E mail registration Android please download from iPhone please download from 1 APP Download 2 Account registration 1 Registe...

Страница 20: ...20 Please set family name and choose location of device Create Family b Register through third party application...

Страница 21: ...21 APP Pairing a With Bluetooth 1 Please confirm that you re connected to Wi Fi and your Bluetooth is on 2 Click Add Device and then follow the instructions to pair device...

Страница 22: ...d release After hearing Beep enter Wi Fi password in app During connection will flash Once the app connects to Wi Fi successfully will display b With Wi Fi 1 Please make sure you are connected to Wi F...

Страница 23: ...r On Off Setting temperature Select Boost Silence Mode 2 For heat pump with Heating Cooling function Compressor speed Query C F switch Setting temperature Select Boost Silence Mode Compressor speed In...

Страница 24: ...ather forecast is just for reference 2 App is subject to updates without notice After pairing if your family members also want to control the device please let your family members register InverGo fir...

Страница 25: ...tor DHP3503 1 14 403771 Sensors full set 1 16 16294 R32 Compressor DHP130 1 16 16296 R32 Compressor DHP170 210 1 16 16304 R32 Compressor DHP280 1 16 16305 R32 Compressor DHP3503 1 16 16292 R32 Compres...

Страница 26: ...26 NOTES...

Страница 27: ...27...

Страница 28: ...their product knowledge and reasonable judgement and will be accepted if a relevant defect is found the warranty claim is made during the relevant warranty period and none of the excluded conditions...

Отзывы: