iBootBar 

– Precision Version 

 

   

Page 14 

iBootBar_Precision_20160428e.doc 

 

Firmware ver 1.41.32 

 

  

 

DTMF Control 

Models with an internal modem <-M suffix> can be controlled from dial up connections using handset dialing tones 
(touch tones).  Use of DTMF control requires a unique PIN number set for each user.  This PIN is set using the 
command line interface and must be 4 to 10 digits long. Program a PIN code of 0 to disable a users ability to use 
DTMF control. 
 

DTMF Call Sequence: 

 

1.  Dial the phone number connected to the iBootBar.  Upon connection a prompt tone will be heard. 

2.  Enter the PIN followed by the # key.  Upon successful entry, a ready tone will be heard.  If no PIN or 

incorrect PIN is received, an error tone and new prompt tone will be issued.  After three unsuccessful 
attempts, the iBootBar will hang up. 

3.  At the ready tone, enter an outlet number 1-8.  The current status of that outlet will be stated in English:  i.e. 

“one on” or “six off”.   

4.  The # key is used to change the state of the outlet.  The * key is used to reboot (or power cycle) the outlet 

for the time configured with the CLI command cycle time.  The new status of the outlet is stated.  If the * key 
is used, the iBootBar will also state ‘begin’ to indicate the reboot or cycle has begun.  

5.  A new prompt tone will indicate that new commands can be entered.  While a reboot is in progress, 

additional outlets can be addressed and commanded. 

6.  The caller can hang up at any time to disconnect the call.  Any reboots in progress will finish their cycle time 

as programmed. 

NOTE: 

Not issuing a command for 5 seconds will cause the iBootBar to hang up. 

 

Notes: 

1.  The only outlets that a caller has access to are determined by the CLI command set user outlet. 

2.  While prompts and voice responses are being played, the iBootBar will not process DTMF tones.  Wait for 

the status and prompts to complete before issuing new commands 

3.  Address an outlet with a number command before entering a control command (# or *) if unsure which outlet 

is being addressed, send the outlet number again.   

4.  Factory Default user admin has default PIN 23646.  Change to desired PIN if maintaining this account.  

Resetting to factory defaults will restore this user and PIN. 

 

Содержание iBootBar iBP-2C10

Страница 1: ...MA 20 Amp 8 x NEMA 5 15 IP Control Serial Control Internal Modem iBP 2N20 2 x NEMA 40 Amp 8 x NEMA 5 15 IP Control Serial Control iBP 2N20 M 2 x NEMA 40 Amp 8 x NEMA 5 15 IP Control Serial Control Int...

Страница 2: ...4 Installation 5 Configuration 7 Basic Operation 9 Command Line Interface Direct Messaging Protocols Advanced Operations 14 Frequent Outlet Control Multi Outlet Control DTMF Control AutoPing Email Not...

Страница 3: ...efeat the safety purpose of the grounding type plug Do not use a 3 to 2 prong adapter at the receptacle use of this type adapter may result in risk of electrical shock and or damage to this product 9...

Страница 4: ...ty The iBP has many features to make the management of power distribution simple and cost effective 8 Independently controllable outlets Dual power inputs for redundant power feeds Support for dual re...

Страница 5: ...the iBP to the standard 19 inch rack Ethernet The iBootBar has a 10 100 Ethernet port The default address is 192 168 0 254 Serial Port The iBootBar has a 9 pin D subminiature connector for RS 232 seri...

Страница 6: ...mum current load for all outlets cannot exceed 12 Amps at 115VAC or 10 Amps when used at 240VAC The iBP 2C10 M is for international applications and can be used on 100V to 240VAC The iBP 2C10 provides...

Страница 7: ...em 2 Automatically from a DHCP Server 3 ARP Ping To configure the mode to set the IP address access the iBootBar command line interface CLI and use the set ipmode command as indicated below Setting th...

Страница 8: ...ted decimal for the iBootBar and the MAC address is the MAC Address of the iBootBar The MAC Address of the iBootBar is located on the rear of the unit Example arp s 63 211 86 165 00 50 c2 05 01 c1 ent...

Страница 9: ...ycle The cycle time is the length of the reboot or power on In seconds 0 99 set cycle n get console Display current console configuration set console timeout 30 3600 disable Console can be set to auto...

Страница 10: ...address of the iBootBar set ipaddress dotted decimal Set the current IP address ipmode must be set to static to use this command set subnet dotted decimal Set the Subnet Mask set gateway dotted decima...

Страница 11: ...e Byte status for each outlets all 8 Bytes of status for each command Verbose Status for controlled outlet only Basic Syntax esc pass esc outlet cmd esc pass outlet cmd CR iPAL Protocol esc pass esc o...

Страница 12: ...Outlet ON C Cycle Outlet Cycle can be On Off On or Off On Off depending on starting status T Set Cycle Time Cycle time in seconds Valid range 1 99 Get Status Outlet number optional No outlet number w...

Страница 13: ...er on or off to improve product life expectancy for example set outlet 1 initial state on set outlet 4 initial state off Multi Outlet Control Command This command is used to operate all eight outlets...

Страница 14: ...e key is used to reboot or power cycle the outlet for the time configured with the CLI command cycle time The new status of the outlet is stated If the key is used the iBootBar will also state begin t...

Страница 15: ...low Upon triggering iBootBar will power off the assigned outlet When the ping response returns iBootBar will power the outlet on Cycle Upon triggering iBootBar will cycle the power to the assigned out...

Страница 16: ...abled using the set upload enable yes command on the console interface To upgrade the iBootBar download the latest version of the firmware and upgrade utility from the Dataprobe website http Dataprobe...

Страница 17: ...M C14 8 x C13 I S M iBP 2C10 2 x C14 8 x C13 I S iBP 2C10 M 2 x C14 8 x C13 I S M iBP C20 C20 8 x C13 I S iBP C20 M C20 8 x C13 I S M iBP 2C20 2 x C20 8 x C13 I S iBP 2C20 M 2 x C20 8 x C13 I S M Key...

Страница 18: ...n for help This device complies with Part 15 of the FCC rules Operation of this device is subject to the following conditions 1 This device may not cause harmful interference and 2 this device must ac...

Страница 19: ...current country setting Note Use of the wrong countrycode violates local laws and the warranty of this product Country countrycode Argentina 07 Australia 09 Austria 253 Belgium 253 Canada 181 China 1...

Страница 20: ...r32 delayTime 2 TB snmpManagerTable 1 TE snmpManagerEntry 1 RO Integer32 snmpManagerIndex 2 RW DisplayString snmpManagerIPAddress 3 RW INTEGER Enum snmpManagerEnable 3 TB outletTable 1 TE outletEntry...

Страница 21: ...Dataprobe Technical Service at 201 934 5111 to receive a Return Materials Authorization RMA Number prior to sending any equipment back for repair Include all cables power supplies and proof of purcha...

Отзывы: