AMT58x-PN ProfiNET®
50
Bit 12 Bit 11 Action
0
X
Normal operating mode.
The encoder will make no change in the output
value.
1
0
Preset mode absolute
The encoder reads the current position value and
calculates an internal offset value from the preset
value
P65000 –Preset value
and the read position
value. The position value is then shifted with the
calculated offset value to get the current position
value equal to the preset value. The encoder
acknowledges the preset by setting the bit 12
Set/shift of home position executed
in the sensor
status word
G1_ZSW
. Now bit 12
Request
set/shift of home position
in the sensor 1 control
word
G1_STW
can be set to zero by the Master.
The encoder will end the preset cycle
by clearing the bit 12
Set/shift of home position
executed
in the sensor status word
G1_ZSW
.The
new internal offset value can be read with an
acyclic data exchange parameter (if implemented)
and is securely stored in case of voltage breakdown
and uploaded again at each power on.
1
1
Preset mode relative (offset)
The encoder uses the preset value
P65000 –
Preset value
as a relative offset value. In this mode
the current position value is shifted by the value
deriving from the preset value.
EXAMPLE
A preset value “1000” is intended to
shift the current position value by 1000
steps in the positive counting direction.
So a “real” position value of “5000” will have the
value “6000” after the relative shifting sequence.
The encoder will set bit 12
Set/shift of home
position executed
in the sensor status word
G1_ZSW
to acknowledge the execution of the
shifting. Bit 12
Request set/shift of home position
in the sensor control word
G1_STW
can now be set
to zero by the Master. The encoder will end the
preset cycle by clearing the bit 12
Set/shift of
home position executed
in the sensor status word
G1_ZSW
.The internal offset value will be shifted
according to the transferred preset value. The new
offset value is securely stored in case of voltage
breakdown and uploaded again at each power on.
The Preset command automatically saves the calculated internal
offset values.
Содержание AMT58*-PN Series
Страница 1: ......
Страница 16: ......
Страница 21: ...AMT58x PN ProfiNET 5 3 1 3 Installation using a flange code ST 58 FLNG ...
Страница 30: ...AMT58x PN ProfiNET 14 Figure 5 Scrolling through Profinet families and categories ...
Страница 114: ...AMT58x PN ProfiNET 98 13 Read write records in acyclic communication Figure 58 Base mode parameter request and response ...
Страница 116: ...AMT58x PN ProfiNET 100 13 1 3 Data Block 1 DB1 Figure 61 DB1 13 1 4 Data Block 2 DB2 Figure 62 DB2 ...
Страница 117: ...AMT58x PN ProfiNET 101 13 1 5 Data Block 3 DB3 Figure 63 DB3 13 1 6 Data Block 4 DB4 Figure 64 DB4 ...
Страница 118: ...AMT58x PN ProfiNET 102 13 1 7 Organization Block 1 OB1 Figure 65 OB1 13 1 8 Function 1 FC1 Figure 66 FC1 ...
Страница 119: ...AMT58x PN ProfiNET 103 Figure 67 FC1 13 1 9 Function 2 FC2 Figure 68 FC2 ...
Страница 123: ...AMT58x PN ProfiNET 107 14 1 Normal operation diagram ...
Страница 124: ...AMT58x PN ProfiNET 108 14 2 Preset diagram ...
Страница 125: ...AMT58x PN ProfiNET 109 14 3 Parking sensor diagram ...
Страница 126: ...AMT58x PN ProfiNET 110 14 4 Error diagram 14 4 1 Acknowledgment of acknowledgeable sensor error ...
Страница 127: ...AMT58x PN ProfiNET 111 14 4 2 Acknowledgment of not acknowledgeable sensor error ...
Страница 145: ......