AMT58x-PN ProfiNET®
38
6.2 Profinet encoders from Datalogic Automation s.r.l.
PROFINET encoders from Datalogic Automation s.r.l. fully comply
with the encoder profile specifications V4.1 version 3.162, the
encoder profile is based on the PROFIdrive profile. For any
information on the encoder profile please refer to the following
document:
ENCODER PROFILE. Technical specifications for Profibus and
Profinet related to PROFIdrive edited by PI International.
Furthermore these encoders fulfil the requirements of the Application
Classes 3 and 4, thus they are intended for clock-synchronous
(isochronous) real-time applications with cyclic and synchronous data
transmission. Anyway they can also be used in applications without
clock synchronization. For detailed information on the application
classes refer to the section “6.3 Application Class definition” on page
41.
PROFINET encoders supports the standard telegrams 81, 82, 83
and 84. Further information can be found in the section “7.1
Telegrams“ on page 44.
The IO data is transferred to and from the Encoder Object (EO, see
the section “6.4 Encoder Object model” on page 42) via the Cyclic
Data Exchange Service. The EO comprises the following mandatory
functionalities:parameters;
measuring task (i.e. position value, velocity value, …);
IO data (cyclical transmission of control and actual values);
support for Alarm Mechanism.
Among the parameters available in the Profinet encoders from
Datalogic Automation: code sequence, scaling function, preset
(Class 4 functionalities), position readout, offset value, velocity value,
velocity measuring unit, acyclic Error Data communication and
diagnostic information.
PROFINET at a glance
Number of
stations
Setting the
IP-
Address
Setting the
baud rate
Transmissio
n rate
Cable
length
Cable
Virtually
unlimited
Software /
automatic
via DCP
-
100 Mbit/s
full duplex
Up to 100
m / 330 ft
M12 D-
coded
Profinet
connectors
Содержание AMT58*-PN Series
Страница 1: ......
Страница 16: ......
Страница 21: ...AMT58x PN ProfiNET 5 3 1 3 Installation using a flange code ST 58 FLNG ...
Страница 30: ...AMT58x PN ProfiNET 14 Figure 5 Scrolling through Profinet families and categories ...
Страница 114: ...AMT58x PN ProfiNET 98 13 Read write records in acyclic communication Figure 58 Base mode parameter request and response ...
Страница 116: ...AMT58x PN ProfiNET 100 13 1 3 Data Block 1 DB1 Figure 61 DB1 13 1 4 Data Block 2 DB2 Figure 62 DB2 ...
Страница 117: ...AMT58x PN ProfiNET 101 13 1 5 Data Block 3 DB3 Figure 63 DB3 13 1 6 Data Block 4 DB4 Figure 64 DB4 ...
Страница 118: ...AMT58x PN ProfiNET 102 13 1 7 Organization Block 1 OB1 Figure 65 OB1 13 1 8 Function 1 FC1 Figure 66 FC1 ...
Страница 119: ...AMT58x PN ProfiNET 103 Figure 67 FC1 13 1 9 Function 2 FC2 Figure 68 FC2 ...
Страница 123: ...AMT58x PN ProfiNET 107 14 1 Normal operation diagram ...
Страница 124: ...AMT58x PN ProfiNET 108 14 2 Preset diagram ...
Страница 125: ...AMT58x PN ProfiNET 109 14 3 Parking sensor diagram ...
Страница 126: ...AMT58x PN ProfiNET 110 14 4 Error diagram 14 4 1 Acknowledgment of acknowledgeable sensor error ...
Страница 127: ...AMT58x PN ProfiNET 111 14 4 2 Acknowledgment of not acknowledgeable sensor error ...
Страница 145: ......