DATAKOM DKG-705 User’s Manual
705_USER.doc
- 40 -
Program Group 6
Group Parameter Definition
Unit Min Max Description
6
600
Reset Maintenance
Counters
-
0
1
Setting this parameter to 1 will
1) Reset the
Time to Service
variable to
Maintenance Period (days) (P625)
value,
2) Reset the
Engine Hours to Service
variable to
Maintenance Period (Engine
Hours) (P624)
value.
This means that a new service period has
started with default values.
The program parameter
P600
itself is not
modified and reads always 0.
6
601
Current Transformer
Primary
A
50 5000 This is the rated value of current
transformers. All transformers must have
the same rating. The secondary of the
transformer will be 5 Amps.
6
602
Low Oil Pr.
Shutdown
Bar
0
4.0 If the oil pressure measured from the
analog input falls below this limit while the
engine is running, this will generate a
Low
Oil Pressure Measured
alarm and shut
down the engine immediately.
6
603
Low Oil Pr. Warning
Bar
0
4.0 If the oil pressure measured from the
analog input falls below this limit while the
engine is running, this will generate a
Low
Oil Pressure Measured Warning
.
6
604
High Temperature
Shutdown
°
C
80 120 If the water temperature measured from the
analog input goes over this limit, this will
generate a
High Coolant Temperature
Alarm
and shut down the engine
immediately.
6
605
High Temp. Warning
°
C
80 120 If the water temperature measured from the
analog input goes over this limit, this will
generate a
High Coolant Temperature
Warning
.
6
606
High Oil T. Shutdown
°
C
80 250 If the oil temperature measured from the
analog input goes over this limit, this will
generate a
High Oil Temperature Alarm
and shut down the engine immediately.
6
607
High Oil T. Warning
°
C
80 250 If the oil temperature measured from the
analog input goes over this limit, this will
generate a
High Oil Temperature
Warning
.
6
608
Low Fuel Level
Shutdown
%
0
50 If the fuel level measured from the analog
input falls below this limit, this will generate
a
Low Fuel Level Alarm
and shut down
the engine immediately.
6
609
Low Fuel Level
Warning
%0
0
50 If the fuel level measured from the analog
input falls below this limit, this will generate
a
Low Fuel Level Warning
.