DATAKOM DKG-705 User’s Manual
705_USER.doc
- 16 -
4.3 Warnings
Definition
Source
Description
Low Oil Press.Switch
Digital Input
High Eng.Temp.Switch
Digital Input
Emergency Stop
Digital Input
Low Coolant Level
Digital Input
Alternator High Temp. Digital Input
High Oil Temp.
Digital Input
Overload
Digital Input
Low Fuel Level
Digital Input
Battery Charger Fail
Digital Input
Spare Alarm 7
Digital Input
Spare Alarm 6
Digital Input
Spare Alarm 5
Digital Input
Spare Alarm 4
Digital Input
Spare Alarm 3
Digital Input
Spare Alarm 2
Digital Input
Spare Alarm 1
Digital Input
These warnings are set depending on the digital input settings. The
related program parameters are
P_700
to
P_776
.
Synchronization Fail
Internal
Set if the phase and voltage synchronization is not successful
before the expiration of
Synchronization Fail Timeout (P_A07)
.
Gen Under-Frequency
Phase-U
Set if the genset frequency goes under the
Low Frequency
Warning (P_517)
limit for
Frequency Timer (P_520)
period.
Gen Over-Frequency
Phase-U
Set if the genset frequency goes over the
High Frequency
Warning (P_519)
limit for
Frequency Timer (P_520)
period.
High Battery Voltage
Internal
Set if the battery voltage goes over the
High Battery Voltage
Warning (P_611)
limit.
Low Fuel Level
Analog
Input
Set if the fuel level measured from analog input goes under the
Low
Fuel Level Warning (P_609)
limit.
High Oil Temperature
Analog
Input
Set if the oil temperature measured from analog input goes over the
High Oil Temperature Warning (P_607)
limit.
High Coolant
Temperature
Analog
Input
Set if the coolant temperature measured from analog input goes
over the
High Coolant Temperature Warning (P_605)
limit.
Low Oil Pressure
Measured
Analog
Input
Set if the oil pressure measured from analog input goes under the
Low Oil Pressure Warning (P_603)
limit.
Mains Phase Sequence
Fail
R-S-T
Set if the mains phase sequence is not correct and
Ignore Phase
Order (P_A06)
parameter is ‘
0
’.
Charge Failure
Charge
input
Set if the
Charge input (terminal_31)
is pulled to battery negative
when the engine is running.
Low Battery Voltage
Internal
Set if the battery voltage goes under the
Low Battery Voltage
Warning (P_612)
limit.
AVR Control Fail
Internal
Set if the
AVR control output
has gone to the low or high limit
value for 1 second.
GOV Control Fail
Internal
Set if the
GOV control output
has gone to the low or high limit
value for 1 second.
Low Engine Speed
Magnetic
Pickup
Set if the engine rpm goes under the
Low rpm Warning (P_614)
limit. If the
Crank Teeth Count (P_619)
is set to ‘0’, this warning will
be disabled.
High Engine Speed
Magnetic
Pickup
Set if the engine rpm goes over the
High rpm Warning (P_616)
limit. If the
Crank Teeth Count (P_619)
is set to ‘0’, this warning will
be disabled.