DATAKOM DKG-705 User’s Manual
705_USER.doc
- 43 -
Group Parameter Definition
Unit Min Max Description
6
629
Emergency Backup
-
0
1
If this parameter is set to 1, in the TEST
mode, the load will be transferred to the
genset if the mains fail.
6
630
Frequency Voltage
Offset
V
5
50 This parameter adjusts the sensitivity for
genset frequency reading. If the genset
frequency appears to be a non-zero value
while the engine is at rest, increase this
parameter. The standard value is 20V.
6
631
Load Shedding Low
Limit
KW
0
5000 If the genset active power output goes
below this limit, then the Load Shedding
relay will be deactivated.
6
632
Load Shedding High
Limit
KW
0
5000 If the genset active power output goes
above this limit, then the Load Shedding
relay will be activated.
6
633
Mains Current
Transformers
-
0
1
0:
Mains current transformers are not
connected. All mains current, power and
cos
Φ
values are zeros,
peak lopping
and
soft transfer to genset
are not allowed
1:
Mains current transformers are
connected and used. All mains current,
power and cos
Φ
measurements are valid,
peak lopping
and
soft transfer to genset
are allowed.
6
634
Modem Connection
-
0
1
0:
No modem connection, the serial port is
connected to PC
1:
Modem connected.