DATAKOM                                                                                 DKG-705 User’s Manual

 

 

 

705_USER.doc 

 

- 47 -   

 

Program Group: 8 

 

 

This group defines the functions of relay outputs. The DKG-705 base unit has 7 relay outputs. The 

relays may be extended up to 23 using 

Relay Extension Modules

 

 

The function of a given relay output may be selected from a list of 112 entries. Here are the usual 

functions of the internal relays. 

 

Group  Parameter  Definition 

Terminal  Description / Usual Function  

800 

Relay 0 function 

This relay output is not provided

 

801 

Relay 1 function 

36 

Auxiliary relay output, mostly used as 

Preheat

 output. 

802 

Relay 2 function 

33 

Start relay output. 

803 

Relay 3 function 

37 

Auxiliary relay output, mostly used as 

Alarm

 output. 

804 

Relay 4 function 

Generator contactor relay output. 

The common terminal of the internal relay is 

connected to the generator phase U. 

 

805 

Relay 5 function 

10 

Mains contactor relay output.  

The common terminal of the internal relay is 

connected to the mains phase R.

 

806 

Relay 6 function 

32 

Fuel relay output.  

 This relay output feeds also the charge 

alternator excitation circuit.

 

807 

Relay 7 function 

35 

Auxiliary relay output, mostly used as 

Activate to 

Stop

 output. 

808 

Relay 8 function 

809 

Relay 9 function 

810 

Relay 10 function 

811 

Relay 11 function 

812 

Relay 12 function 

813 

Relay 13 function 

814 

Relay 14 function 

815 

Relay 15 function 

These relays are found on the first 

Relay Extension 

Module

816 

Relay 16 function 

817 

Relay 17 function 

818 

Relay 18 function 

819 

Relay 19 function 

820 

Relay 20 function 

821 

Relay 21 function 

822 

Relay 22 function 

823 

Relay 23 function 

These relays are found on the second 

Relay 

Extension Module

 

Содержание DKG-705

Страница 1: ...mable relay outputs 7 I O expansion capability LCD display 4 lines by 20 characters Periodic maintenance request indicator True RMS AC measurements Built in exerciser Remote Start capability Statistic...

Страница 2: ...tion mode 5 2 Remote start operation 6 SYNCHRONIZING WITH MAINS 6 1 Governor Control 6 2 AVR Control 7 LOAD TRANSFER MODES 7 1 Transfer with Interruption 7 2 No Break Transfer 7 3 Soft Transfer 8 PARA...

Страница 3: ...s current phase S optional Mains current phase T optional Mains frequency Mains KW phase R optional Mains KW phase S optional Mains KW phase T optional Mains KVA phase R optional Mains KVA phase S opt...

Страница 4: ...nt transformers shall be 5 Amperes The input current rating of the current transformers may be selected as needed between 50 5 and 5000 5 amps Current transformer outputs shall be connected by separat...

Страница 5: ...remove the plug connectors when inserting wires with a screwdriver 2 ALWAYS refer to the National Wiring Regulations when conducting installation 3 An appropriate and readily accessible set of disconn...

Страница 6: ...set applications in order to provide extra security the normally closed contact of the mains contactor should be serially connected to this output In no break transfer or parallel with mains applicati...

Страница 7: ...Analogue oil pressure sensor connection Do not connect the sensor to other devices 19 FUEL LEVEL SENSOR Input 0 5000 ohms Analogue fuel level sensor connection Do not connect the sensor to other devi...

Страница 8: ...REHEAT Output 10A 28VDC 37 RELAY 3 ALARM RELAY Output 10A 28VDC These relays have programmable functions selectable from a list Term Function Technical data Description 38 CURR_R 39 CURR_R 40 CURR_S 4...

Страница 9: ...NERATOR Yellow The LED will turn on when all 3 generator phase voltages are within the programmed limits LOAD GENERATOR Yellow It turns on when the generator contactor is activated LOAD MAINS Green It...

Страница 10: ...the given situation If an alarm or warning occurs during operation other then programming mode the display will automatically switch to ALARM LIST position The MENU button will not allow to switch to...

Страница 11: ...chronoscope Governor Output I AVR Output Voltage RU Phase Angle degrees Phase U Voltage Genset Frequency Phase R Voltage Mains Frequency 2 5 Soft transfer parameters Remaining Duration Governor Output...

Страница 12: ...P_625 If any of the programmed values is zero this means that the parameter will not be used For example a maintenance period of 0 days indicates that the DKG 705 will request maintenance only based...

Страница 13: ...ese conditions cause The alarm relay output to operate The WARNING led to turn on Most of the alarms are of LATCHING type Even if the alarm condition is removed the alarms will stay on and disable the...

Страница 14: ...Analog In Set if the coolant temperature measured from analog input goes over the High Coolant Temperature Shutdown P_604 limit Low Oil Pressure Measured Analog In Set if the oil pressure measured fro...

Страница 15: ...Input Spare Alarm 3 Digital Input Spare Alarm 2 Digital Input Spare Alarm 1 Digital Input These load dump alarms are set depending on the digital input settings The related program parameters are P_70...

Страница 16: ...if the fuel level measured from analog input goes under the Low Fuel Level Warning P_609 limit High Oil Temperature Analog Input Set if the oil temperature measured from analog input goes over the Hig...

Страница 17: ...No Mains Frequency R In parallel with mains operation and after the parallel check timeout delay P_A23 has elapsed this warning will be set if the mains frequency disappears for more than 2 5 periods...

Страница 18: ...ration of the genset will be as in the OFF mode LOAD TEST It is used to test the genset under load Once this mode is selected the engine will run and the load will be transferred to the genset The gen...

Страница 19: ...e REMOTE START signal is absent then mains voltages will be supposed to be present The front panel mimic diagram s mains LEDs will reflect the status of the REMOTE START input Any of the digital input...

Страница 20: ...Enable This parameter enables disables the activation of the governor control output If governor control is disabled the output will always stay at the rest level defined by P_A13 P_A03 GOV Reverse Po...

Страница 21: ...control is disabled the output will always stay at the rest level defined by P_A14 P_A05 AVR Reverse Polarity In normal polarity the AVR control impedance decreases in order to increase the alternato...

Страница 22: ...ere will be a power interruption period duration during the transfer Note that the program parameters P_508 and P_509 define the power interruption period If this transfer method is used it is advised...

Страница 23: ...The difference between mains and genset frequencies not more than programmed limit The voltage difference between phase R and phase U not more than programmed limit The phase angle between phase R and...

Страница 24: ...No Break Transfer This parameter enables disables the No Break Transfer feature P_A06 Ignore Phase Order If set this parameter will disable the phase order check The phase order check should be disabl...

Страница 25: ...g parallel with mains operation the mains contactor will immediately deenergize a general Parallel Mains Fail warning and a specific protection function warning will be generated At the end of the Sof...

Страница 26: ...he genset after start The unit includes a comprehensive set of protection functions to detect quickly a mains failure during parallel with mains operation The protections are enabled after the timeout...

Страница 27: ...and GOV controllers without extra hardware different power ratings acceptable for both gensets single genset load enabling slave genset run stop depending on user defined power levels and time delays...

Страница 28: ...f frequency The ROCOF measures the frequency of the mains for each period If the frequency change exceeds the predefined limit for 4 successive periods the ROCOF detects a mains failure Thus the respo...

Страница 29: ...power detector has a variable response time For a power not exceeding 2 times the predefined limit the response time is 8 cycles The response time is reduced with larger reverse powers It is approxim...

Страница 30: ...my load function consists on the connection of a dummy load if the total genset load is below a limit and to disconnection of the dummy load when the total power exceeds another limit The dummy load f...

Страница 31: ...ion of the genset is disabled by the weekly schedule then the AUTO led will flash instead of a steady on state Each turn on turn off time is defined in 15 minute steps These parameters are defined in...

Страница 32: ...f exercise has come the unit will automatically switch to either TEST or LOAD TEST mode The engine will run and if the on load exercise is selected then the load will be transferred to the genset If a...

Страница 33: ...nt The events are always displayed starting from the most recent one The Event Logging screens are included in menu group 3 Switching from one menu group to another is made by holding the MENU button...

Страница 34: ...ts inside the unit Wipe the unit if necessary with a soft damp cloth Do not use chemical agents 17 SOFTWARE DOWNLOAD The DKG 705 application software is held in a flash memory and is field downloadabl...

Страница 35: ...next program parameter in the current group if the current parameter is not modified This means that after modification the MENU key should be pressed twice to switch to the next parameter After the l...

Страница 36: ...efine the function of 24 possible relays 9 Sensor calibration 2 Calibration points information for each of the 4 analog sensor inputs A Operation Mode 3 No Break transfer parallel with mains AVR and G...

Страница 37: ...urns on for starting the genset 5 501 Wait before Start Sec 0 30 This is the time after the fuel solenoid is energized and before the genset is started This will be the preheat period if glow plugs ar...

Страница 38: ...Gen High Limit Volt 100 300 If one of the generator phase voltages goes over this limit when feeding the load this will generate a Genset High Voltage Alarm and the engine will stop 5 516 Low Freq Sh...

Страница 39: ...DATAKOM DKG 705 User s Manual 705_USER doc 39 5 522 Mains Freq Low Limit Hz 0 60 AUTO TEST 5 523 Mains Freq High Lim Hz 44 70 AUTO TEST 5 524 Genset Voltage Fail Timer Sec 0 30...

Страница 40: ...g input falls below this limit while the engine is running this will generate a Low Oil Pressure Measured Warning 6 604 High Temperature Shutdown C 80 120 If the water temperature measured from the an...

Страница 41: ...6000 If engine speed measured from the magnetic pickup input goes over this limit this will generate a High rpm Warning 6 617 Excess Power Load dump KW 0 2500 If the genset load goes over this limit...

Страница 42: ...aintenance from being omitted If the period is set to 0 no SERVICE REQUEST will be indicated depending on engine hours however service may still be requested on a time limit basis see also parameter P...

Страница 43: ...5000 If the genset active power output goes below this limit then the Load Shedding relay will be deactivated 6 632 Load Shedding High Limit KW 0 5000 If the genset active power output goes above thi...

Страница 44: ...n t care and the exercise will be performed every day regardless of the day selection If the monthly exercise is selected with parameter P_638 2 then the exercise will be performed during the first 7...

Страница 45: ...dump alarm 2 Warning 3 No alarm given from this input 7 7x2 Digital input x delay 0 1 0 Delay 1 second 1 Delay 4 seconds This is the alarm detection speed of the input If the parameter is set to 1 the...

Страница 46: ...Spare Alarm 6 11 Spare Alarm 5 12 Spare Alarm 4 13 Spare Alarm 3 14 Spare Alarm 2 15 Spare Alarm 1 16 Mains Contactor Switch This signal is used for No Break transfer operation 17 Genset Contactor Swi...

Страница 47: ...y output The common terminal of the internal relay is connected to the generator phase U 8 805 Relay 5 function 10 Mains contactor relay output The common terminal of the internal relay is connected t...

Страница 48: ...put_4 053 Load Dump Digital Input_5 054 Load Dump Digital Input_6 055 Load Dump Digital Input_7 No FUNCTION 056 Load Dump not used 057 Load Dump not used 058 Load Dump not used 059 Load Dump not used...

Страница 49: ...stics are defined using a maximum of 8 known points Each point consists of a pair of value the first being the resistor value and the second being the corresponding analog measurement For each sensor...

Страница 50: ...ore Phase Order 0 1 0 Phase order check enabled This option is used in 3 phase gensets 1 Phase order check disabled This option is used in single phase gensets 10 A07 Synchronization Fail Timeout Sec...

Страница 51: ...t and mains phases during synchronization The standard value for this parameter is 64 But it must be readjusted for the genset during manufacturing If this parameter is too high a voltage oscillation...

Страница 52: ...tion while operating in parallel with mains When the parallel protections are enabled if the phase of the mains measured on last 2 cycles jumps over this limit on the phase measured on last 4 th and 5...

Страница 53: ...e Genset Power Rating defined in parameter P_A17 10 A37 Dual Genset Delayed Stop Power 0 100 If the total active load is below this level for the period defined in P_A38 the slave genset will stop Thi...

Страница 54: ...on 11 B01 Phase S Calibration 11 B02 Phase T Calibration 11 B03 Phase U Calibration 11 B04 Phase V Calibration 11 B05 Phase W Calibration 11 B06 Current R Calibration 11 B07 Current S Calibration 11 B...

Страница 55: ...the load is transferred to the mains AC voltages displayed on the unit are not correct Check engine body grounding The error margin of the unit is 3 volts If there are faulty measurements only when t...

Страница 56: ...Y and charging alternator D terminal The normally closed contact of the relay will be connected serially to the unit s START output So the starting will also be removed when the D pulls to battery pos...

Страница 57: ...be 20 seconds Check the synchronization limits P_A10 P_A11 P_A12 If necessary widen the limits A typical application may be P_A10 0 5Hz P_A11 5V P_A12 5 20 DECLARATION OF CONFORMITY The unit conforms...

Страница 58: ...pouts survives 0V for 100ms Current consumption 500 mA DC max Relay outputs open Total DC Current Output Rating 10A DC Max Current for each Terminal 10A RMS Magnetic pickup voltage 0 5 to 70Vpk Magnet...

Страница 59: ...DATAKOM DKG 705 User s Manual 705_USER doc 59 22 CONNECTION DIAGRAM...

Страница 60: ...DATAKOM DKG 705 User s Manual 705_USER doc 60 DATAKOM Electronics Limited Tel 90 216 466 84 60 Fax 90 216 364 65 65 e mail datakom datakom com tr http www datakom com tr...

Отзывы: