DKG-519 User Manual V-27
(14.04.2011)
- 6 -
Term Function
Technical data
Description
21
EMERGENCY STOP
Digital inputs
These
inputs
have
programmable
characteristics selected via the program
menu. Each input may be driven by a
‘normally closed’ or ‘normally open’ contact,
switching either or battery-. The effect
of the switch is also selectable from a list. See
PROGRAMMING section for more details.
22
SPARE-2
23
PROGRAM LOCK
24
SPARE-1
25
COOLANT LEVEL
26
HIGH TEMP
27
LOW OIL PRESSURE
28
RECTIFIER FAIL
29
Current
transformer
inputs, 5A-AC
Connect the generator current transformer
terminals to these inputs. Do not connect the
same current transformer to other instruments
otherwise a unit fault will occur. Connect each
terminal of the transformer to the unit’s related
terminal. Do not use common terminals. Do
not use grounding. Correct polarity of
connection is vital. If the measured power is
negative, then change the polarity of each 3
current transformers. The rating of the
transformers should be the same for each of
the 3 phases. The secondary winding rating
shall be 5 Amperes. (For ex. 200/5 Amps).
30
CURR_1-
31
32
CURR_2-
33
34
CURR_3-
35
OIL TEMP. SENDER
Input, 0-5000 ohms
Analogue oil temperature sender connection.
Do not connect the sender to other devices.
The input has programmable characteristics
and connects to any kind of sender.
36
MAGNETIC PICKUP
Inputs, 1-30V
0-8KHz
Connect the magnetic pickup signal to these
inputs.
37
MAGNETIC PICKUP