6.10 Service Request Display
This led is designed to help the periodic maintenance of the genset to be made consistently.
The periodic maintenance is basically carried out after a given engine hours (for example 200
hours), but even if this amount of engine hours is not fulfilled, it is performed after a given time limit (for
example 12 months).
The SERVICE REQUEST led has no effect on the genset
operation.
The unit has both programmable engine hours and maintenance time limit. The engine hours is
programmable with 50-hour steps, the time limit is programmable with 1 month steps. If any of the
programmed values is zero, this means that the parameter will not be used. For example a maintenance
period of 0 months indicates that the unit will request maintenance only based on engine hours, there will
be no time limit. If the engine hours is also selected as 0 hours this will mean that the SERVICE
REQUEST display will be inoperative.
When the engine hours
OR
the time limit is over, the
SERVICE REQUEST
led (red) will start to
flash and the service request relay function will be active.
The service request relay function may be assigned to spare relays using
Relay Definition
program parameters. Also relays on an extension module may be assigned to this function.
To turn off the SERVICE REQUEST led, and reset the service
period, press together the ALARM MUTE and LAMP TEST keys
for 5 seconds.
The remaining engine hours and the remaining time limit are kept stored in a non-volatile memory
and are not affected from power supply failures.
The time and engine hours to service are displayed in the
STATISTICAL COUNTERS
menu.
6.11 Engine Hour Meter
The unit features a non-erasable incremental engine hour meter. The hour meter information is
kept in a non-volatile memory and is not affected from power supply failures.
The engine hours may be displayed
STATISTICAL COUNTERS
menu.
6.12 Date & Time Display
The date & time display is provided for verification.
6.13 Software Version Display
Some additional features are installed within consecutive software releases. In order to be
sure of the validity of the status of the unit, the software version needs to be known.
The software version of the unit is displayed together with the data – time information.
The software version consists of 2 numbers. The first number represent the operating software
version of the unit.