DKG-379 User Manual Rev_02
V-15
(24-12-2012)
K43D01-EN - 57 -
Parameter Definition,
(Password Level)
Unit
Factory
Set
Description
(1)
Low Oil Pressure
Warning
bar
1.4
If the oil pressure measured from the analog input
falls below this limit, this will generate a
LOW OIL
PRESSURE SENDER
warning.
(2)
Low Oil Pressure
Shutdown
bar
1.0
If the oil pressure measured from the analog input
falls below this limit, this will generate a
LOW OIL
PRESSURE SENDER
alarm is generated and the
engine stops.
(1)
High Temperature
Warning
°C
95
If the coolant temperature measured from the analog
input goes over this limit, this will generate a
HIGH
TEMPERATURE SENDER
warning.
(2)
High Temperature
Shutdown
°C
98
f the coolant temperature measured from the analog
input goes over this limit, this will generate a
HIGH
TEMPERATURE SENDER
alarm and the engine will
stop.
(2)
Oil Pressure Sender type
-
1
This parameter selects the oil pressure sender type.
0:
Non standard sender. The sender characteristics
are defined in
Sender Characteristics
table.
1:
VDO 0-7 bars (10-180 ohms)
2:
VDO 0-10 bars (10-180 ohms)
3:
DATCON 0-7 bars (240-33 ohms)
4:
DATCON 0-10 bars (240-33 ohms)
5:
DATCON 0-7 bars (0-90 ohms)
6:
DATCON 0-10 bars (0-90 ohms)
7:
DATCON 0-7 bars (75-10 ohms)
(2)
Coolant Temp. Sender
Type
-
1
This parameter selects the temperature sender type:
0:
The sender characteristics are defined in
Sender
Characteristics
table.
1:
VDO
2:
DATCON DAH type
3:
DATCON DAL type
(2)
Engine Heating
Temperature
°C
0
If it is requested that the engine runs without load
until reaching a certain temperature, this parameter
defines the temperature.
If the coolant temperature falls below this parameter,
an
Engine Low Temperature
warning will occur.
(2)
Engine Start Delay
sec
0
This is the time between the battery bank voltage
falls below the set limit and the fuel solenoid turns on
before starting the genset.
(2)
Preheat Timer
sec
1
This is the time after the fuel solenoid is energized
and before the genset is started. During this period
the
PREHEAT
relay output is energized (if assigned
by
Relay Definitions
)
(2)
Crank Timer
sec
10
This is the maximum start period. Starting will be
automatically cancelled if the genset fires before the
timer.
(2)
Wait Between Starts
sec
10
This is the waiting period between two start attempts.
(1)
Engine Heating Timer
sec
4
This is the period used for engine heating following
the program parameter.
(1)
Cooldown Timer
min
1.0
This is the period that the generator runs for cooling
purpose after the load contactor is released.
15.3. ENGINE PARAMETERS GROUP