DKG-379 User Manual Rev_02
V-15
(24-12-2012)
K43D01-EN - 18 -
Structure:
Differential frequency measurement input, MPU or charging pulses
Input impedance:
100 k-ohms
Input voltage:
1.0VAC-RMS to 100VAC-RMS
Frequency range:
10Hz to 10 kHz
Resolution:
1 rpm
Accuracy:
0.2% + 1 rpm (±3rpm @1500 rpm)
Flywheel teeth range:
1 to 500
Do not share MPU with other devices.
If charge alternator pulses are used, please connect
only the MPU+ terminal and leave open the MPU-
terminal.
If MPU unit is used, then use a twisted cable pair or
coaxial cable for best results.
3.10. MAGNETIC PICKUP INPUT