DKG-379 User Manual Rev_02                                

                         

   V-15 

(24-12-2012)       

 

 

 

K43D01-EN                                                 - 54 -                                              

 

 

 

 

Parameter Definition, 

(Password Level) 

Unit 

Factory 
Set 

Description 

(2)

 Current Shunt Rating 

60 

This is the rated value of the current shunt at 60mV-
DC output voltage.   

(2)

 Overcurrent Limit 

If the current goes above this limit, during the period 
defined in 

Overload Timeout

 then a 

Overcurrent 

Load Dump

 alarm will be generated.  

If this parameter is 0 then Overcurrent check is 
disabled. 

(2)

 Excess Power Limit 

KW 

If the active power goes above this limit, during the 
period defined in Overload Timeout then an 

Excess 

Power Load Dump 

alarm will be generated.  

If this parameter is 0 then Excess Power check is 
disabled. 

(2)

 Overload Timeout 

sec 

This is the period between the current or active power 
go over the limits and 

OVERCURRENT 

or

 EXCESS 

POWER

 Load Dump alarms occur.  

This is also the period between the engine rpm goes 
out of the limits and 

OVERSPEED 

or

 UNDERSPEED 

alarms occur. 
This is also the period between the alternator voltage 
goes out of the limits and 

HIGH VOLTAGE 

or

 LOW 

VOLTAGE 

alarms occur. 

(2)

 Genset Low Voltage 

Warning Limit 

9.0 

If the battery bank DC voltage goes under this limit, 
this will generate a 

GENSET LOW VOLTAGE

 

warning. 

(2)

 Genset High Voltage 

Warning Limit 

63.0 

If the battery bank DC voltage goes above this limit, 
this will generate a 

GENSET HIGH VOLTAGE

 

warning. 

(2)

 Genset High Voltage 

Shutdown Limit 

66.0 

If the battery bank DC voltage goes under this limit, 
this will generate a 

GENSET HIGH VOLTAGE 

alarm 

and the engine will stop. 

(2)

 Low Battery Voltage 

Warning 

9.0 

If the battery voltage falls below this limit, this will 
generate a 

LOW BATTERY 

warning. 

(2)

 High Battery Voltage 

Warning 

15.5 

If the battery voltage goes over this limit, this will 
generate a 

HIGH BATTERY 

warning. 

(2)

 High Battery Voltage 

Shutdown 

16.5 

If the battery voltage goes over this limit, this will 
generate a 

HIGH BATTERY 

shutdown

 

alarm and 

the engine will stop. 

(2)

 Genset Contactor Timer 

sec 

This is the period after the mains contactor has been 
deactivated and before the generator contactor has 
been activated. 

(1)

 Start to Charge Voltage 

24.0 

When the battery bank voltage falls below this level 
during 

CHARGE VOLTAGE THRESHOLD

 timer, 

then the controller will initiate an automatic charging 
cycle. The default value is set for a 24V battery 
bank. 

(1)

 Max Charge Current 

50 

This is the maximum allowed charge current flowing 
from the alternator to the battery bank. 

(1)

 Max Charge Time 

min 

120 

This is the maximum duration of a charge cycle. 
Even if the charge cycle is not completed at the 
expiration of this timer, the engine will stop. 

(1)

 Nominal Charge Volt 

27.4 

This is the float charge voltage of the battery bank. 
The default value is set for a 24V battery bank. 

15.2. ELECTRICAL PARAMETERS GROUP

 

Содержание DKG-379

Страница 1: ...started the controller will perform an optimal battery charging cycle and will stop the genset when batteries are fully charged The optimal charge algorithm allows maximum battery life and minimal eng...

Страница 2: ...installation of genset control units which reduce future issues For all technical queries please contact Datakom at below e mail address datakom datakom com tr FILENAME DESCRIPTION 379_INSTE DKG 379 I...

Страница 3: ...rdering the correct version DKG 379 MPU G T 00 Screw type bracket Stock Code J10P01 per unit Self Retaining type bracket Stock Code K16P01 per unit Sealing Gasket Stock Code K44P01 SPARE PARTS ORDERIN...

Страница 4: ...of the unit Fuses must be of fast type FF with a maximum rating of 6A Disconnect all power before working on equipment Any electrical parameter applied to the device must be in the range specified in...

Страница 5: ...NBUS PORT 3 13 RS 232 PORT OPTIONAL 4 CONNECTION DIAGRAM 5 TERMINAL DESCRIPTION 6 TECHNICAL SPECIFICATIONS 7 DESCRIPTION OF CONTROLS 7 1 FRONT PANEL FUNCTIONALITY 7 2 PUSHBUTTON FUNCTIONS 7 3 DISPLAY...

Страница 6: ...FINITIONS 15 9 INPUT FUNCTION SELECT 15 10 SITE ID STRING 15 11 MODEM1 2 SMS1 2 3 4 TELEPHONE NUMBERS 16 CRANK CUTTING 17 J1939 CANBUS ENGINE SUPPORT 18 SOFTWARE FEATURES 18 1 Charging the Engine Batt...

Страница 7: ...perature in any case Below conditions may damage the device Incorrect connections Incorrect power supply voltage Voltage at measuring terminals beyond specified range Voltage applied to digital inputs...

Страница 8: ...DKG 379 User Manual Rev_02 V 15 24 12 2012 K43D01 EN 8 Dimensions 172x134x76mm 6 8 x5 3 x3 0 Panel Cutout 151x111mm minimum 6 0 x4 4 Weight 450g 1 lb 2 1 DIMENSIONS 2 MOUNTING...

Страница 9: ...ould not be able to access parts of the unit other than the front panel Mount the unit on a flat vertical surface Before mounting remove the mounting brackets and connectors from the unit then pass th...

Страница 10: ...2012 K43D01 EN 10 Two different types of brackets are provided Screw type bracket Self retaining type bracket Installation of screw type bracket Installation of self retaining type bracket Do not tig...

Страница 11: ...oreign objects of 1 0 mm diameter and greater 5 Protected from the amount of dust that would interfere with normal operation 6 Dust tight 2nd Digit Description of Protection Level 0 Not protected 1 Pr...

Страница 12: ...rature range Use adequate cable section at least 0 75mm2 AWG18 Follow national rules for electrical installation Current shunts must have 60mV output at nominal current For the correct operation of th...

Страница 13: ...voltage protection Withstands 150VDC continuously Reverse voltage 33VDC continuous Maximum operating current 250mA 12 24VDC All options included digital outputs open Typical operating current 200mA 12...

Страница 14: ...50VDC Measurement method Isolated DC voltage measurement Sampling rate 100 Ks s Input voltage range 0 to 100 mVDC Measurement range 0 to 100 mVDC Input impedance 1000 ohms Isolation 500VAC 1minute Ac...

Страница 15: ...hold 35 of battery voltage High level threshold 85 of battery voltage Maximum input voltage 100VDC with respect to battery negative Minimum input voltage 70VDC with respect to battery negative Noise f...

Страница 16: ...y 2 0 1V 0 9V 30VDC Charge Fail Warning Threshold adjustable Charge Fail Shutdown Alarm Threshold adjustable Open circuit voltage battery positive Overvoltage protection 500VDC continuous with respect...

Страница 17: ...switching power 4000VA Structure linear output for rpm voltage control Functionality Precision PID control output regulating rpm voltage for voltage matching current control temperature and rpm limiti...

Страница 18: ...S to 100VAC RMS Frequency range 10Hz to 10 kHz Resolution 1 rpm Accuracy 0 2 1 rpm 3rpm 1500 rpm Flywheel teeth range 1 to 500 Do not share MPU with other devices If charge alternator pulses are used...

Страница 19: ...must be battery negative Any function can be assigned to digital inputs Digital outputs can be extended using DKG 186 Fet Extension modules each one providing 8 outputs Digital outputs have the same...

Страница 20: ...ance 200m with 120 ohm balanced cable Description RS 232 non isolated Functionality External modem PC connection PLC connection Connector RJ11 6pin Connection 6 wires Rx Tx DTR CxD GND 10V Full duplex...

Страница 21: ...DKG 379 User Manual Rev_02 V 15 24 12 2012 K43D01 EN 21 4 CONNECTION DIAGRAM...

Страница 22: ...an 70VDC otherwise the unit may get damaged 4 DC LOAD POSITIVE TERMINAL 5 DC ALTERNATOR OUTPUT POSITIVE 6 LOAD CONTACTOR NO TERMINAL Relay output 16A DC This output provides energy to the load contact...

Страница 23: ...sender connection Do not connect the sender to other devices The input has programmable ohms for VDO senders 19 OIL PRESSURE SENDER Input 0 5000 ohms Analogue oil pressure sender connection Do not co...

Страница 24: ...mally open contact switching either battery or battery The effect of the switch is also selectable from a list See PROGRAMMING section for more details 27 SPARE 2 28 PROGRAM LOCK 29 SPARE 1 30 COOLANT...

Страница 25: ...max Alternator voltage 0 to 70V DC Battery bank voltage 0 to 70V DC Current input from DC shunt 60mV at rated current Rated Current range 1 to 5000 ADC at 60mV Actuator Output Voltage 0 to 12 24V Actu...

Страница 26: ...FUNCTIONALITY 7 DESCRIPTION OF CONTROLS Fault condition indicators Service request indicator TEST mode button RUN mode button AUTO mode button STOP mode button Graphic LCD screen LAMP TEST if held pre...

Страница 27: ...The genset runs when necessary and starts charging Selects OFF mode The genset stops BUTTON FUNCTION LAMP TEST when held pressed Selects next item or decrease value in program mode Selects previous di...

Страница 28: ...ss ALARM MUTE button first If there is more than one alarm the next alarm is displayed by pressing the button Thus all existing alarms can be scanned When there is no more alarm to display END OF ALAR...

Страница 29: ...ist If no alarm exists END OF ALARM LIST will be displayed Existing alarms load_dumps warnings and J1939 ECU warnings will be displayed as one screen for each entry Switching to the next entry will be...

Страница 30: ...pired MODE LEDS Each led turns on when the related mode is selected either locally or remotely MIMIC DIAGRAM LEDS LOAD CONTACTOR ON Turns on when the load contactor is activated GENSET RUNNING This le...

Страница 31: ...voltages L1 L2 L3 Mains frequency Digital input statuses Charge input status J1939 VAlues if applicable event number event type fault definition see below for various event sources date and time oper...

Страница 32: ...displayed Skip the password entry screen by pressing the button 4 times The screen below left will come Press again button The last event is displayed The first page will display the event number even...

Страница 33: ...incremental counters for statistical purposes The counters consist on total genset kWh total engine hours total engine cranks total engine runs engine hours to service time to service These counters...

Страница 34: ...g under load then it will be immediately unloaded The engine will continue to run during Cooldown Timer and will stop afterwards If the STOP button is pressed again then the engine will immediately st...

Страница 35: ...s during crank timer When the engine fires the crank relay will be immediately deactivated See section Crank Cutting for more details The engine will run at idle speed during Idle Speed Timer The engi...

Страница 36: ...op the engine press button or select another mode of operation The TEST mode is entered by pressing the button The TEST mode is used in order to test the genset under load Once this mode is selected t...

Страница 37: ...le Even if the charge cycle is not completed at the expiration of this timer the engine will stop 1 Nominal Charge Volt V 27 4 This is the float charge voltage of the battery bank The default value is...

Страница 38: ...loop A high value will cause slower but more stable operation A low value will cause faster operation but may cause instability 1 RPM High Limit rpm 2000 This is the maximum allowed rpm of the engine...

Страница 39: ...r is closed Thus load switching is performed with zero current This provides longer contactor life Step_C The controller increases the rpm slowly until reaching the maximum charging current Step_D The...

Страница 40: ...oltage If connected the controller will take into account the battery bank temperature The temperature sensor is of industry standard PT100 type not provided with the controller During the charging cy...

Страница 41: ...nt 0 If this value is different from zero when the charge current falls below this percentage of the max charge current then the charge cycle will be supposed to be terminated If this parameter is set...

Страница 42: ...s closed The genset starts the charging of the battery bank The charge current is not controlled Step_D The battery bank voltage increases slowly until reaching the nominal genset DC output voltage St...

Страница 43: ...e Alarms operate in a first occurring basis If a shutdown alarm is present following shutdown alarms loaddumps and warnings will not be accepted If a loaddump is present following loaddumps and warnin...

Страница 44: ...LOW OIL PRESSURE Set if a signal is detected at the Low Oil Pressure Switch input or the oil pressure value measured from the sender is below the programmed limit Warning and alarm limits are separat...

Страница 45: ...he timer then no alarm will be set EXCESS POWER Set if the genset power KW supplied to the load goes over the Excess Power limit for Overload Timer If the power goes below the limit before expiration...

Страница 46: ...oil pressure sender input This fault will be monitored with Holdoff Timer delay after the engine is running Also if the oil pressure switch is open at the beginning of a start attempt then the engine...

Страница 47: ...EST and ALARM MUTE Hold pressed ALARM MUTE The program mode is used to adjust timers operational limits and the configuration of the unit Although a free PC program is provided for programming every p...

Страница 48: ...t supports 3 password levels The level_1 is designed for field adjustable parameters The level_2 is designed for factory adjustable parameters The level_3 is reserved It allows recalibration of the un...

Страница 49: ...vailable parameters will be displayed Selected parameter is shown in reverse video blue on white In order display change the value of this parameter please press MENU button Parameter value may be inc...

Страница 50: ...election keys If no button is pressed during 2 minutes the program mode will be cancelled automatically 14 4 MODIFYING PARAMETER VALUE 14 5 PROGRAMMING MODE EXIT Press any mode button Decrease paramet...

Страница 51: ...on small characters 3 screen 8 or 9 Details of each screen are explained in chapter 3 2 2 Fault Holdoff Timer sec 12 This parameter defines the delay after the engine runs and before the fault monitor...

Страница 52: ...ST mode 1 Exercise at LOAD TEST mode 1 Exercise Period 1 0 exercise every day the exercise will be performed every day regardless of the day selection of Exercise Dat and Time parameter 1 exercise onc...

Страница 53: ...S on Load Status Change 0 This parameter controls SMS sending when load contactor status is changed No warning is generated 0 no SMS when load contactor status is changed 1 SMS sent when load contacto...

Страница 54: ...s above this limit this will generate a GENSET HIGH VOLTAGE warning 2 Genset High Voltage Shutdown Limit V 66 0 If the battery bank DC voltage goes under this limit this will generate a GENSET HIGH VO...

Страница 55: ...ines the reaction speed of the actuator output A high gain will cause faster reaction but brings a risk of instability A low gain is slower to react but more stable 2 PID Stability Percent 10 This par...

Страница 56: ...alls below the Battery Start to Charge Voltage during this timer then the controller will initiate an automatic charging cycle 1 Must Start Voltage V 0 0 When the battery bank voltage falls below this...

Страница 57: ...6 DATCON 0 10 bars 0 90 ohms 7 DATCON 0 7 bars 75 10 ohms 2 Coolant Temp Sender Type 1 This parameter selects the temperature sender type 0 The sender characteristics are defined in Sender Characteris...

Страница 58: ...ne hours 1 Service Period month 6 The SERVICE REQUEST led indicator will turn on after this amount of time from the last service If the period is set to 0 no SERVICE REQUEST will be indicated dependin...

Страница 59: ...ctive 2 High Oil Temperature Warning C 100 If the oil temperature measured from the analog input goes over this limit this will generate a HIGH OILTEMPERATURE SENDER warning 2 High Oil Temperature Shu...

Страница 60: ...4 112 CATERPILLAR ADEM II III 128 SCANIA S6 129 SCANIA Single Speed 130 SCANIA All Speed 144 IVECO 160 MTU MDEC 302 161 MTU MDEC 201 162 MTU MDEC 303 163 MTU MDEC 304 164 MTU MDEC 505 176 BOSCH Generi...

Страница 61: ...hour Seconds 00 59 Current second of the minute Parameter Definition Unit Factory Set Description Monday Turn_on 24 00 Please review chapter 9 for a detailed description of weekly programming schedule...

Страница 62: ...C value Temperature Sender Ohms 3 ohm 134 Temperature Sender point 3 ohm value Temperature Value 3 C 60 Temperature Sender point 3 C value Temperature Sender Ohms 4 ohm 322 Temperature Sender point 4...

Страница 63: ...Level Sender point 2 value Fuel Level Sender Ohms 3 ohm 67 Fuel Level Sender point 3 ohm value Fuel Level Value 3 50 Fuel Level Sender point 3 value Fuel Level Sender Ohms 4 ohm 110 Fuel Level Sender...

Страница 64: ...1 Battery positive Response delay 0 0 No delay 1 Delayed 4sec Parameter Definition Unit Fac Set Description Action 0 0 Shutdown the engine stops immediately 1 Load Dump the engine stops after cooldown...

Страница 65: ...ative 1 Battery positive Response delay 0 0 No delay 1 Delayed 4sec Parameter Definition Unit Fac Set Description Action 0 0 Shutdown the engine stops immediately 1 Load Dump the engine stops after co...

Страница 66: ...negative 1 Battery positive Response delay 0 0 No delay 1 Delayed 4sec Parameter Definition Unit Fac Set Description Action 0 0 Shutdown the engine stops immediately 1 Load Dump the engine stops afte...

Страница 67: ...ne stops after cooldown 2 Warning the horn relay operates 3 No operation Sampling 1 0 Always 1 After holdoff timer 2 When mains present Latching 1 0 Non latching 1 Latching Contact type 0 0 Normally o...

Страница 68: ...nction expansion module 1 selected from list Relay 07 Definition 0 RELAY 7 function expansion module 1 selected from list Relay 08 Definition 2 RELAY 8 function expansion module 1 selected from list R...

Страница 69: ...larm 55 Low fuel sender alarm 56 High oil temp alarm 57 58 59 High battery voltage alarm 60 Charge fail alarm 61 62 63 64 Oil switch load_dump 65 Temp switch load_dump 66 Coolant Level switch load_dum...

Страница 70: ...lant Level switch Input 04 Function Select 3 Rectifier Fail Input 05 Function Select 4 Emergency Stop Input 06 Function Select 11 Spare 1 Input Input 07 Function Select 10 Spare 2 Input Input Function...

Страница 71: ...in order to enable dialing through a pabx If Modem Enabled This is the first telephone number used for modem calls If Modem Disabled This is the first SMS telephone number Program Group Modem 2 SMS 2...

Страница 72: ...d level 2 Parameter Definition Factory Set Description SMS 3 telephone number This SMS telephone number accepts up to 16 digits Program Group SMS 5 Telephone Number password level 2 Parameter Definiti...

Страница 73: ...Parameters Charge Input Connected 1 If the charge alternator voltage reaches Engine Parameters Crank Cut Charge Voltage then cranking is immediately stopped Oil pressure above threshold Following set...

Страница 74: ...1 Engine Brand ECU Type J1939 SW version 2 Engine Coolant Level 3 Engine Oil Level 4 Engine Coolant Pressure 5 Engine Fuel Delivery Pressure 6 Barometric Pressure 7 Engine Crankcase Pressure 8 Engine...

Страница 75: ...essure sensor fail 168 x Battery voltage failure 172 x High inlet air temperature High inlet manifold air temperature Inlet manifold air temperature sensor fail 174 x High fuel temperature Fuel temper...

Страница 76: ...ve 7 Mechanical fault Faulty response from mechanical system 8 Mechanical or electrical fault Abnormal frequency 9 Communication fault Abnormal updating rate or Open circuit in injector circuit 10 Mec...

Страница 77: ...output functions of the Relay Definitions group should be set properly RELAY 1 terminal_23 and RELAY 2 terminal_22 have programmable functions selected from a list Digital outputs may be increased usi...

Страница 78: ...Start signal input Any digital input may be assigned as Disable Auto Start using Input Function Select program parameters It is also necessary to set the ACTION program parameter of the related input...

Страница 79: ...also the Disable Auto Start feature Please review related chapter for a detailed explanation of this feature Priority In Dual Genset Mutual Standby Operation It may be required that the dual genset sy...

Страница 80: ...o the exerciser are Exercise start day and hour Exercise duration Exercise off_load on_load Please refer to the programming section for a more detailed description of the above parameters When the sta...

Страница 81: ...eating Method parameter is set to 0 In this mode the engine will run during parameter Engine Heating Timer and then the genset will take the load 2 Timer and temperature controlled heating This operat...

Страница 82: ...the chassis and has a limited capacity The fuel level reference is measured through the analog fuel level sender When the measured fuel level falls below Fuel Pump Low Limit parameter the fuel pump o...

Страница 83: ...n Modbus Protocol Reference Guide This document may be downloaded at www modbus org docs PI_MBUS_300 pdf ADDRESS hex R W DATA SIZE COEFFICIENT DESCRIPTION 0003 R 16bit x10 Genset DC voltage 0004 R 16b...

Страница 84: ...oaddump alarm bits bit_0 oil pressure switch loaddump alarm bit_1 high temperature switch loaddump alarm bit_2 coolant level switch loaddump alarm bit_3 rectifier fail loaddump alarm bit_4 emergency s...

Страница 85: ...contactor bit_1 crank relay bit_2 spare_2 bit_3 spare_1 bit_5 fuel 003A R 16bit Relay extension module relay statuses bit_0 module_1 relay_1 status bit_1 module_1 relay_2 status bit_2 module_1 relay_...

Страница 86: ...aiting before between cranks 3 cranking 4 engine heating 5 load contactor timer 6 load on genset 8 cooldown operation 9 stopping 0040 R W 8bit Last pressed key This byte is also used in order to chang...

Страница 87: ...1460 days 0060 R 16bit x8 J1939 Engine speed 0061 R 16bit x1 J1939 Coolant temperature 40 C offset 0062 R 16bit x10 J1939 Oil pressure 0063 0064 R 16bit x20 J1939 Total engine hours 0065 R 16bit x100...

Страница 88: ...utput 1026 R 8bit x1 Operation mode_2 bits bit_0 modem connected bit_1 exercise on load bit_3 2 bit_4 bit_5 rpm from genset frequency bit_6 sms enable bit_7 GPRS connectio006E 1027 R 8bit x50 Engine h...

Страница 89: ...electronic equipment WEEE this unit should be stored and disposed separately from the usual waste The european ROHS directive restricts and prohibits the use of some chemical materials in electronic d...

Страница 90: ...e oil pressure switch closes very lately As the unit senses an oil pressure it does not start When oil pressure switch closes the unit will start Optionally the oil pressure switch may be replaced The...

Страница 91: ...d Check that the genset Yellow led is on steadily Adjust genset voltage and frequency limits if necessary Check that the digital output 8 is configured as Genset Contactor Check Genset Contactor Timer...

Отзывы: