DKG-379 User Manual Rev_02
V-15
(24-12-2012)
K43D01-EN - 60 -
Parameter Definition,
(Password Level)
Unit Factory
Set
Description
(2)
J1939 Enable
-
0
0: The J1939 port is inoperative.
1: The analog measurements (oil, temp, rpm) are
picked_up from the ECU. If the ECU communication is
lost, then the engine will be stopped.
(2)
J1939 Engine Type
-
0
00:
GENERIC ENGINE TYPE
16:
CUMMINS CM850
32:
DETROIT DIESEL
48:
DEUTZ Generic
49:
DEUTZ EMR2
50:
DEUTZ EMR3
64:
JOHN DEERE
80:
PERKINS
81:
PERKINS ADEM 3
82:
PERKINS ADEM 1.3
96:
VOLVO (with CIU unit)
97:
VOLVO EMS2
98:
VOLVO EDC4
112:
CATERPILLAR ADEM II/III
128:
SCANIA S6
129:
SCANIA Single Speed
130:
SCANIA All Speed
144:
IVECO
160:
MTU MDEC 302
161:
MTU MDEC 201
162:
MTU MDEC 303
163:
MTU MDEC 304
164:
MTU MDEC 505
176:
BOSCH Generic
177:
BOSCH EDC 731
178:
BOSCH EDC 9.3
Other values:
Reserved. Do not use.
(2)
J1939 Speed Adjust
%
50
This parameter adjusts the speed of an ECU controlled
engine by +/- 8%.
(2)
VOLVO Speed Toggle
-
-
This program parameter is not stored, but only used in
order to activate the primary or secondary speed
selection operation of a Volvo EMS-II engine control
unit.
0: Initiate the primary speed select operation
1: Initiate the secondary speed select operation
Below parameters are applicable to J1939 enabled
versions only.
15.3. ENGINE PARAMETERS GROUP (continued)