DKG-379 User Manual Rev_02
V-15
(24-12-2012)
K43D01-EN - 46 -
GENSET LOW / HIGH
SPEED
Set if the engine rpm is outside programmed limits. These faults will be
monitored with
Holdoff Timer
delay after the engine is running. Low and
high limits for warning and alarm are separately programmable. Another
high engine rpm shutdown limit which is 12% above the high limit is always
monitored and stops the engine immediately.
GENSET LOW / HIGH
VOLTAGE
Set if the battery bank DC voltage goes outside programmed limits for
Overload Timer
. This fault will be monitored with
holdoff timer
delay after
the engine is running.
LOW / HIGH BATTERY
VOLTAGE
Set if the genset battery voltage is outside programmed limits.
FAIL TO STOP
Set if the engine has not stopped before the expiration of the
Stop Timer
.
LOW CHARGE VOLTAGE
Set if a charge alternator failure (or broken belt) occurs. This fault condition
may result to a
warning
or
alarm
following programming.
J1939 ECU FAIL
Set when an engine fault code is received from the ECU of the electronic
engine. This fault will not cause an engine stop. If necessary, the engine will
be stopped by the ECU.
LOW OIL PRESSURE
Set if a signal is detected at the Low Oil Pressure Switch input or the oil
pressure value measured from the sender is below the programmed limit.
Warning and alarm limits are separately programmable for the oil pressure
sender input. This fault will be monitored with
Holdoff Timer
delay after the
engine is running. Also if the oil pressure switch is open at the beginning of
a start
attempt, then the engine will not be started and “
Oil Pressure
Exists!
” information is displayed. When the oil pressure switch closes,
normal operation will be resumed.
HIGH TEMPERATURE
Set if a signal is detected at the High Temperature Switch input or the
coolant temperature value measured from the sender is above the
programmed limit. Warning and alarm limits are separately programmable
for the temperature sender input.
LOW TEMPERATURE
Set if the coolant temperature value measured from the sender is blow the
Engine Heating Temperature
limit.
LOW FUEL
Set if a signal is detected at the low fuel level input or the the fuel level
measured from the sender is below the programmed limit. Warning and
alarm limits are separately programmable for the fuel level sender input.
EMERGENCY STOP
Set if a signal is detected at the emergency stop input.
SPARE-1 / SPARE-2
Set if a signal is detected from the related spare fault input.
SERVICE REQUEST
Set if the service counter has expired. In order to reset the service
counters please hold pressed both with
and
buttons during 5
seconds. The screen will display “Completed!”
SHORT CIRCUIT
PROTECTION ACTIVE
Set if the actuator output is short circuited or overloaded. When the short
circuit is removed, the unit will automatically revert to normal operation.
However this warning will persist and must be reset manually.
13.3. WARNINGS