DKG-379 User Manual Rev_02
V-15
(24-12-2012)
K43D01-EN - 25 -
DC Supply Range:
9.0 to 33.0 V-DC
Cranking dropouts:
survives 0 V for 100ms.
Typical Standby Current:
200 mA-DC
Maximum Operating Current:
250 mA-DC (outputs open)
Load Contactor Relay Output:
16 A / 250V-AC / 30V-DC
DC Outputs:
1A @ 28V protected semiconductor outputs
Charge excitation:
min 2 Watts
Analog Output:
Output Range:
0-10V-DC
Output Impedance:
1K-ohms
Max Load:
10K-ohms
Digital Inputs:
0 to 33V-DC
Analog sender input range:
0-5000 ohms.
Battery Temp. Input:
standard PT100 sensor
Magnetic pickup input::
1.0
– 100VAC-RMS
Magnetic pickup frequency:
10 KHz max.
Alternator voltage:
0 to 70V-DC
Battery bank voltage:
0 to 70V-DC
Current input:
from DC shunt, 60mV at rated current
Rated Current range:
1 to 5000 ADC at 60mV
Actuator Output Voltage:
0 to 12/24V
Actuator Drive:
7A-DC max, current limited, short circuit and thermally protected.
Actuator Short Circuit Protection:
min 9 Amp
Serial port:
RS-232, 9600 bauds, no parity, 1 bit stop
Operating temp.:
-20
°C (-4°F) to 70°C (158°F).
Storage temp.:
-40
°C (-40°F) to 80°C (176°F).
Maximum humidity:
95% non-condensing.
Dimensions:
172 x 134 x 76 mm (WxHxD)
Panel Cut-out Dimensions:
151x111 mm minimum.
Weight:
450 g (approx.)
Case Material:
High Temperature ABS/PC (UL94-V0)
IP Protection:
IP65 from front panel, IP30 from the rear
CE Conformity reference standards:
EN 61010 (safety requirements)
EN 61326 (EMC requirements)
6. TECHNICAL SPECIFICATIONS