Parameter Definition,
(Password Level)
Unit Factory
Set
Description
(1)
Real Time Clock Adjust
-
117
This parameter trims precisely the real time clock
circuit.
Values from 0 to 63 speed up the clock with
0.25sec/day steps.
Values from 127 to 64 slow down the clock with
0.25sec/day steps.
(2)
Crank Teeth Count
-
30
This is the number of pulses generated by the
magnetic pickup sensing unit in one turn of the
flywheel.
This parameter is also used in the conversion of the
genset frequency to engine rpm. The frequency in Hz
is multiplied with this parameter during conversion to
rpm.
(2)
SMS on Load Status
Change
-
0
This parameter controls SMS sending when load
contactor status is changed. No warning is
generated.
0:
no SMS when load contactor status is changed
1:
SMS sent when load contactor status is changed
(2)
Fuel Pump Low Limit
%
20
If the fuel level measured from the sender input falls
below this level, then the FUEL PUMP function will
become active.
(2)
Fuel Pump High Limit
%
80
If the fuel level measured from the sender input goes
above this level, then the FUEL PUMP function will
become passive.
(2)
Oil pressure sender fault
effect
-
0
0: no effect
1:warning
2:loaddump
(2)
Coolant temp sender fault
effect
-
0
0: no effect
1:warning
2:loaddump
(2)
Fuel level sender fault
effect
-
0
0: no effect
1:warning
2:loaddump
(2)
Oil temp sender fault
effect
-
0
0: no effect
1:warning
2:loaddump
15.1. CONTROLLER CONFIGURATION GROUP (continued)