D-500 MK2 User Manual Firmware V-6.3
- 66 -
Alternator voltage:
0 to 300 V-AC (Ph-N)
Alternator frequency:
0-600 Hz.
Mains (Busbar) voltage:
0 to 300 V-AC (Ph-N)
Mains (Busbar) frequency:
0-600 Hz.
Topology:
1-2-3 phases, with or without neutral
DC Supply Range:
8.0 to 36.0 V-DC.
DC power consumption:
300 mA-DC typical @12V-DC
150 mA-DC typical @24V-DC
600 mA-DC max. @12V-DC
300 mA-DC max. @24V-DC
V-A-cos Accuracy:
0.5% + 1 digit
KW-kVA-kVAr Accuracy:
1.0% + 1 digit
CT Range:
5/5A to 5000/5A
VT Range:
0.1/1 to 6500 / 1
kW Range:
0.1kW to 65000 kW
Current Inputs:
from current transformers. ../5A.
Digital inputs:
input voltage 0 to 36 V-DC.
Analog input range:
0-5000 ohms.
Digital Outputs:
Protected mosfet semiconductor outputs, rated 1Amp@28V-DC
Cranking dropouts:
survives 0V for 100ms.
Magnetic pickup voltage:
0.5 to 30VAC.
Magnetic pickup frequency:
0 to 10000 Hz.
GOV Control Output:
0-10V-DC
AVR Control Output:
±3V-DC, fully isolated
Charge Alternator Excitation:
2W.
Display Screen:
2.9
”, 128x64 pixels
Ethernet Port:
100 Mbits
USB Device:
USB 2.0 Full speed
USB Host:
USB 2.0 Full speed
RS-485 Port:
selectable baud rate
Data Link Port:
Fully Isolated CANBUS
Operating temperature:
-
20°C to 70°C (-4 to +158 °F)
Storage temperature:
-
40°C to 80°C (-40 to +176°F)
Maximum humidity:
95% non-condensing.
IP Protection:
IP54 from front panel, IP30 from the rear.
Dimensions:
200 x 148 x 46mm (WxHxD)
Panel Cut-out Dimensions:
176 x 121 mm minimum.
Weight: -----
Case Material:
High Temperature, non-flammable ABS/PC
Mounting:
Front panel mounted with rear retaining plastic brackets.
EU Directives Conformity
-2014/35/EC (low voltage)
-2014/30/EC (electro-magnetic compatibility)
Norms of reference:
EN 61010 (safety requirements)
EN 61326 (EMC requirements)
UL / CSA Conformity:
-
UL 6200, Controls for Stationary Engine Driven Assemblies (Certificate # - 20140725-E314374)
CSA Compatibility:
-CAN/CSA C22.2 No. 14-13
– Industrial Control Equipment
9. TECHNICAL SPECIFICATIONS
Содержание D-500 MK2
Страница 40: ...D 500 MK2 User Manual Firmware V 6 3 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Страница 41: ...D 500 MK2 User Manual Firmware V 6 3 41 5 4 3 PHASE 4 WIRE DELTA 5 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 ...
Страница 43: ...D 500 MK2 User Manual Firmware V 6 3 43 5 9 1 PHASE 2 WIRE 5 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 53: ...D 500 MK2 User Manual Firmware V 6 3 53 7 1 GENSET SYNCHRONIZATION FUNCTIONALITY 7 CONNECTION DIAGRAMS ...
Страница 54: ...D 500 MK2 User Manual Firmware V 6 3 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Страница 55: ...D 500 MK2 User Manual Firmware V 6 3 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Страница 56: ...D 500 MK2 User Manual Firmware V 6 3 56 7 4 AMF FUNCTIONALITY ...
Страница 57: ...D 500 MK2 User Manual Firmware V 6 3 57 7 5 ATS FUNCTIONALITY ...
Страница 58: ...D 500 MK2 User Manual Firmware V 6 3 58 7 6 REMOTE START FUNCTIONALITY ...
Страница 59: ...D 500 MK2 User Manual Firmware V 6 3 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Страница 60: ...D 500 MK2 User Manual Firmware V 6 3 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Страница 72: ...D 500 MK2 User Manual Firmware V 6 3 72 ...