D-500 MK2 User Manual Firmware V-6.3
- 110 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
GCB Alarm Level
-
0
1
0
0:
shutdown alarm
1:
loaddump alarm
Genset MCB Fail Timer
sec
0
600
2.0
If a genset MCB feedback input is
defined and if the genset MCB fails to
change position before the expiration of
this timer, then a fault condition occurs.
Genset Phase Order
Check Enable
-
0
1
0
0:
genset phase order checking
disabled
1:
if genset phase order is faulty, then a
genset phase order fail loaddump alarm
is given.
Busbar Fail Timer
sec
0
30
2.0
When a genset closes to the Busbar, if
the mater genset controller does detect
the Busbar voltage at the expiration of
this period, a “BUSBAR FAIL” fault
condition will occur.
Busbar Ready Timer
sec
0
30
2.0
This is the delay after all generators
close to the busbar and before the
master genset controller acknowledges
“Busbar ready” signal.
Multi Load Subtract
Power Level
kW
0
65000
0
When the genset active power goes
over this limit, the controller will start
substracting load as described in
chapter
Five Step Load Management
.
Multi Load Add Power
Level
kW
0
65000
0
When the genset active power goes
below this limit, the controller will start
adding load as described in chapter
Five Step Load Management
.
Multi Load Substract
Start Delay
sec
0
36000
0
If the load stays over the
Multi Load
Substract Power Level
parameter
during this timer, then 1 step of load is
substracted.
Multi Load Substract
Wait Delay
sec
0
36000
0
This is the minimum period between
two load subtract operations.
Multi Load Add Start
Delay
sec
0
36000
0
If the load stays below the
Multi Load
Add Power Level
parameter during this
timer, then 1 step of load is added.
Multi Load Add Wait
Delay
sec
0
36000
0
This is the minimum period between
two load add operations.
Excess power Warning
Limit
kW
0
50000
0
If the genset active power goes above
this limit then the controller will give an
Excess Power Warning.
17.2. ELECTRICAL PARAMETERS GROUP (continued)
Содержание D-500 MK2
Страница 40: ...D 500 MK2 User Manual Firmware V 6 3 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Страница 41: ...D 500 MK2 User Manual Firmware V 6 3 41 5 4 3 PHASE 4 WIRE DELTA 5 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 ...
Страница 43: ...D 500 MK2 User Manual Firmware V 6 3 43 5 9 1 PHASE 2 WIRE 5 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 53: ...D 500 MK2 User Manual Firmware V 6 3 53 7 1 GENSET SYNCHRONIZATION FUNCTIONALITY 7 CONNECTION DIAGRAMS ...
Страница 54: ...D 500 MK2 User Manual Firmware V 6 3 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Страница 55: ...D 500 MK2 User Manual Firmware V 6 3 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Страница 56: ...D 500 MK2 User Manual Firmware V 6 3 56 7 4 AMF FUNCTIONALITY ...
Страница 57: ...D 500 MK2 User Manual Firmware V 6 3 57 7 5 ATS FUNCTIONALITY ...
Страница 58: ...D 500 MK2 User Manual Firmware V 6 3 58 7 6 REMOTE START FUNCTIONALITY ...
Страница 59: ...D 500 MK2 User Manual Firmware V 6 3 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Страница 60: ...D 500 MK2 User Manual Firmware V 6 3 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Страница 72: ...D 500 MK2 User Manual Firmware V 6 3 72 ...