In this mode, the transfer will be made
without power interruption from genset to mains
. This implies
that both of the mains and generator contactors will be active during transfer.
The maximum duration that both contactors will be active is programmable. However this process may be
quicker with the use of one auxiliary feedback contact from each contactor. Thus the changeover will be
quite instantaneous, preventing any excess or reverse power condition.
To prevent a phase to phase short circuit below criteria must be met:
-The mains and generator voltages must be equal,
-The mains and generator voltages must have the same phase,
-The mains and generator voltages must have the same phase sequence.
The unit will allow an
Uninterrupted Transfer
only if
all
of the below conditions are fulfilled:
-Mains phase voltages within the programmed limits,
-Mains frequency within the programmed limits,
-Genset phase voltages within the programmed limits,
-Genset frequency within the programmed limits,
-Mains phase order correct (or phase order check must be disabled),
-Genset phase order correct (or phase order check must be disabled),
-The difference between mains and genset frequencies not more than programmed limit,
-The voltage difference mains-L1 and genset-L1 not more than programmed limit,
-The phase angle between mains-L1 and genset-L1 not more than programmed limit,
When an uninterrupted transfer cycle is started, the unit will wait until the expiration of the
Synchronization Fail Timer
, to find a matching frequency, phase and voltage.
Usually, with frequencies matching at +/- 2Hz and voltages matching at +/-10 volts an
Uninterrupted
Transfer
is expected to successful.
If matching is found before the expiration of the
Synchronization Fail Timer
, then both contactors will be
activated. If contactor auxiliary contacts are used, the other contactor will release immediately. If
contactor auxiliary contacts are not used, the other contactor will release after
contactor timeout
.
The unit offers below parameters for the setup of the Uninterrupted transfer feature.
Parameter Definition Description
No Break Transfer
Enable
0:
only interrupted transfer enabled
1:
no break transfer enabled
Synchronization Fail
Timeout
If the phase and voltage synchronization is not successful before the
expiration of this timer, then a
Synchronization Fail
warning is given and the
transfer will be performed with interruption.
Synchronization
Contactor Timeout
When synchronization is detected, both contactors will stay closed during this
timer.
Max Freq Difference
This is the maximum difference between mains and genset frequencies to
close both contactors.
Max Volt Difference
This is the maximum difference between the mains phase-L1 and the genset
phase-L1 voltages to close both contactors. If voltage transformer is used, this
quantity is multiplied with voltage transformer ratio.
Max Phase Difference
This is the maximum phase angle between the mains phase-L1 and the
genset phase-L1 voltages to close both contactors.
Phase Offset
This parameter is used to compensate the phase angle introduced by voltage
transformers in case of MV synchronization. This angle value is added to the
phase differential during phase matching process.
29.2. UNINTERRUPTED TRANSFER
Содержание D-500 MK2
Страница 40: ...D 500 MK2 User Manual Firmware V 6 3 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Страница 41: ...D 500 MK2 User Manual Firmware V 6 3 41 5 4 3 PHASE 4 WIRE DELTA 5 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 ...
Страница 43: ...D 500 MK2 User Manual Firmware V 6 3 43 5 9 1 PHASE 2 WIRE 5 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 53: ...D 500 MK2 User Manual Firmware V 6 3 53 7 1 GENSET SYNCHRONIZATION FUNCTIONALITY 7 CONNECTION DIAGRAMS ...
Страница 54: ...D 500 MK2 User Manual Firmware V 6 3 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Страница 55: ...D 500 MK2 User Manual Firmware V 6 3 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Страница 56: ...D 500 MK2 User Manual Firmware V 6 3 56 7 4 AMF FUNCTIONALITY ...
Страница 57: ...D 500 MK2 User Manual Firmware V 6 3 57 7 5 ATS FUNCTIONALITY ...
Страница 58: ...D 500 MK2 User Manual Firmware V 6 3 58 7 6 REMOTE START FUNCTIONALITY ...
Страница 59: ...D 500 MK2 User Manual Firmware V 6 3 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Страница 60: ...D 500 MK2 User Manual Firmware V 6 3 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Страница 72: ...D 500 MK2 User Manual Firmware V 6 3 72 ...